GE SF6 Instruction Manual page 184

With spring operating mechanisms
Table of Contents

Advertisement

Replacing the densimeter
Process
08- 2016
Maintenance
Electrical contact densimeter threshold inspection
The table below gives the process to replace the densimeter:
Step
Action
1
Disconnect the pipe (12)
from the valve (24) of the
connection valve block (5).
Screw the valve- cap (25) on
the valve (24).
2
Remove the densimeter (1),
held in place by screws (14),
on the connection valve
block (5).
3
Remove
the
valve block (5), held in place
by screws (8), on the housing
cover (2) of the circuit-
breaker.
NOTE:
If the connection
valve
block
more used, see the next
paragraph
the control tool".
4
Install new seals (26) and
(27) on the densimeter (1),
referring to "Preparing and
installing static seals" in
"Erection general proced-
ures".
Install the densimeter (1) on
the housing cover (2), of the
circuit- breaker,
screws (8).
GE Information
12
5
1
connection
2
(5)
is
any
5
"Putting
away
2
27
26
using
1
Diagram
24
25
5
x3
14
H M6-20
x3
8
H M6-20
x3
8
H M6-20
0,7 daN.m
L51- 108EN/06