Introduction
The Undervoltage Release (UVR) accessory, shown in Figure
1, can be installed in 800–4000 ampere frame Power Break®
II circuit breakers. This accessory trips the circuit breaker when
the input control voltage drops to 35–60% of its rated value
and prevents an open breaker from closing until the input
control voltage is greater than 80% of the rated value.
In addition to providing a trip signal to the breaker, the UVR
accessory can be set up to interact with other Power Break II
accessories, when used with a MicroVersaTrip Plus™ o r
MicroVersaTrip PM™ Trip Unit. DIP switches on the rear of
the breaker Trip Unit can configure the UVR accessory to
activate a Bell Alarm–Alarm Only accessory or a Bell Alarm
with Lockout accessory when a UVR trip occurs. The Accessory
Configuration section below describes how this can be done. If
the breaker is equipped with a Power+™ Trip Unit, it is
configured so that only protection trips will activate a Bell
Alarm–Alarm Only or Bell Alarm with Lockout.
The catalog numbers for the UVR for various voltage
applications are listed in Table 1.
Figure 1. Undervoltage Release.
Operation
Apply control voltage to terminals 29 and 30 of the terminal
strip on the right side of the breaker. When the applied control
voltage is above 80% of the UVR's rated value, the breaker can
be closed. When the voltage drops to 35–60% of the rated
value, the UVR will trip the breaker.
Courtesy of store.ips.us
GEH–6285C
®
Power Break
Accessories
Undervoltage Release
Catalog
Voltage
Rating ❿
Number
SPUV012DC
12 Vdc
SPUV024DC
24 Vdc
SPUV048DC
48 Vdc
SPUV125DC
125 Vdc
SPUV250DC
250 Vdc
SPUV024AC
24 Vac
SPUV048AC
48 Vac
SPUV120AC
120 Vac
SPUV208AC
208 Vac
SPUV240AC
240 Vac
24–240 Vac devices are rated for 50/60 Hz.
Peak inrush current is present for 2–6 ms after activation. This
number is provided so that fuses and supplies can be chosen
appropriately.
Table 1. Catalog numbers and voltages for the Undervoltage Release.
Installation
WARNING: Before installing any accessories, turn the breaker
OFF, disconnect it from all voltage sources, and discharge the
charging springs.
AVERTISSEMENT: Avant d'installer toute accessoire, mettre
le disjoncteur en position OFF, le déconnecter de toute tension
d'alimentation, et décharger les ressorts d'armement.
The Undervoltage Release is installed in the accessory
compartment through the front of the circuit breaker in the
position shown in Figure 2.
Figure 2. Accessory compartment on front of circuit breaker, with
Undervoltage Release slot indicated.
II Circuit Breaker
Peak Inrush
Nominal RMS
Current, A ❡
Current, mA
19
15
7.5
3
1.5
15
7.5
3
1.9
1.5
300
140
70
30
15
370
210
80
60
45

Advertisement

loading

Summary of Contents for GE GEH-6285C

  • Page 1 GEH–6285C ® Power Break II Circuit Breaker Accessories Undervoltage Release Introduction Catalog Voltage Peak Inrush Nominal RMS Rating ❿ Current, A ❡ Number Current, mA The Undervoltage Release (UVR) accessory, shown in Figure SPUV012DC 12 Vdc 1, can be installed in 800–4000 ampere frame Power Break® SPUV024DC 24 Vdc II circuit breakers.
  • Page 2 Use the following procedure to install the UVR accessory into Unit. If the breaker is equipped with a Power+ Trip Unit, the the UVR slot in the accessory compartment of the circuit factory default settings, listed in Table 2, can not be changed. breaker: The UVR accessory can be configured to activate the Bell 1.
  • Page 3 Description of Switch Settings 7. Pull the Trip Unit locking lever to the right. While holding the lever, carefully align the connector on the rear Following are descriptions of the effects of each accessory switch of the Trip Unit with the connector in the breaker. Press when it is enabled: down on the Trip Unit, while holding it near the battery 1.
  • Page 4 Should further information be desired o r should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company. GE Electrical Distribution & Control General Electric Company 41 Woodford Ave., Plainville, CT 06062...

This manual is also suitable for: