Model
Description
Main Breaker
Generator Breaker
Only qualified personnel should be working on the panel box
An amateur should NEVER open the panel box
Please follow all rules and regulations of the National Electric Code
Step 1: Disassemble the interlock. Place the bottom plate (holes only) at edge of main breaker and this will line up with the bottom
edge of the generator breaker and mark holes as in picture below.
Step 2: Turn off the main breaker and remove the panel cover.
Step 3: Drill holes as marked on panel cover with supplied 3/16 drill bit and remove all burs from drilling cover.
Step 4: Insert screws from rear of cover, install bottom plate, and install top plate (slotted) install thread lock to screws and install
retaining nuts. Ensure proper movement.
Step 5: Install 2 pole Generator breaker below main breaker and place Generator Warning Sticker on Generator breaker.
SD200SA
Generator Interlock Kit on BR 100 amp panel
200 Amp Horizontal throw 4 Handle Main Breaker
Below Main
WARNING

Advertisement

loading

Summary of Contents for GE SD200SA

  • Page 1 SD200SA Model Generator Interlock Kit on BR 100 amp panel Description 200 Amp Horizontal throw 4 Handle Main Breaker Main Breaker Below Main Generator Breaker WARNING Only qualified personnel should be working on the panel box An amateur should NEVER open the panel box Please follow all rules and regulations of the National Electric Code Step 1: Disassemble the interlock.