Multi-strings starting sequence: please start up the last string (from communication
structure, the last slave string, see the table blow) of battery system first, one by one to the
first string which shall be started up lastly. Details as below table.
Communication Structure
Master string
*
Slave string 1
Slave string 2
Slave string 3
Slave string 4
Slave string 5
* BMS of the rack with Link Port 0 EMPTY is defined as the Master string, which communicates with the
inverter or upper controller. In one system, there's ONLY ONE Master string, the rest are defined as the
slave strings.
Black start function: When the system is turned on, and relay is OPEN, press the Start Button
more than 10 secs. Then relay will be CLOSE for about10mins without communication
(depending on conditions).
Multi-strings Black Start: Black start operation is ONLY needed to be performed on Mater
string. And it will close circuit for one of the strings within the system for 10mins. The slave
string black start function is ONLY controlled by master string.
Wi-Fi
Manufacturer: Pylon Technologies Co., Ltd.
Address: Plant 8, No.505 Kunkai Road, JinXi Town, 215324 Kunshan City, Jiangsu Province,
PEOPLE'S REPUBLIC OF CHINA
Importer: XXXX (Located in installed country)
Address: XXXX (Located in installed country)
Wireless Max. Output Power
Operating frequency
Gain of antenna
Modulation system
Modulating Repetition
Channel spacing
Type of antenna
Starting Sequence
Last Start up
5th Start up
4th Start up (if has)
3rd Start up (if has)
2nd Start up (if has)
1st Start up (if has)
Basic Information of Wi-Fi
15dBm
2412-2472MHz
Max 3dBi
DBPSK/DQPSK/CCK(DSSS)
BPSK/QPSK/16QAM/64QAM(OFDM)
1Mbps/2Mbps/5.5Mbps/11Mbps (DSSS)
6Mbps/9 Mbps/12 Mbps/18 Mbps/24 Mbps/36 Mbps/48
Mbps/54 Mbps (OFDM)
MCS0~MCS7 (802.1 1n 20MHz)
5MHZ
2.4G IPEX-SMA Antenna