Starting Frequency (Pr. 13); Load Pattern Selection (Pr. 14) - Mitsubishi Electric FR-A520-0.4K-NA Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-A520-0.4K-NA:
Table of Contents

Advertisement

z

Starting frequency (Pr. 13)

Pr. 13 "starting frequency"
You can set the starting frequency between 0 and 60Hz.
Set the starting frequency at which the start signal is switched on.
z
Parameter
Factory Setting
Number
13
0.5Hz
<Setting>
Output frequency
(Hz)
60
Pr.13
0
Forward
rotation
Note: The inverter will not start if the frequency setting signal is less than the value set in Pr. 13 "starting
frequency".
For example, when 5Hz is set in Pr. 13, the motor will start running when the frequency setting signal
reaches 5Hz.
z

Load pattern selection (Pr. 14)

Pr. 14 "load pattern selection"
You can select the optimum output characteristic (V/F characteristic) for the application and load
characteristics.
Parameter
Factory Setting
Number
14
Pr.14=0
For constant-torque loads
(e.g. conveyor, cart)
100%
Base frequency
Output frequency (Hz)
Setting Range
0.01 to 60Hz
Frequency setting signal (V)
ON
Setting Range
0
0 to 5
Pr.14=1
For variable-torque loads
(Fan, pump)
100%
Base frequency
Output frequency (Hz)
Time
Pr. 0 "torque boost"
Pr. 80 "motor capacity"
Pr. 81 "number of motor poles"
Pr. 180 to Pr. 186
Pr.14=2
For lift
Boost for forward rotation...Pr. 0 setting
Boost for reverse rotation...0%
100%
Forward
rotation
Reverse
rotation
Pr.0
Base frequency
Output frequency (Hz)
70
PARAMETERS
Related parameters
(input terminal function selection)
Pr.14=3
For lift
Boost for forward rotation...0%
Boost for reverse rotation...Pr. 0 setting
100%
Reverse
rotation
Forward
rotation
Pr.0
Base frequency
Output frequency (Hz)