Access To Head Internal Part; Combustion Head Adjustment - Riello DB16 LSM C13 Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burner, two stage progressive or modulating operation
Table of Contents

Advertisement

Available languages

Available languages

4.9

Access to head internal part

 Disconnect the plug of the pneumatic valve implementing oil
lance;
 disconnect oil pipes 1) and 2)(Fig. 16) and remove the
nozzle 3);
 remove the fastening screws 5) of the cover;
4.10

Combustion head adjustment

In order to maximize the performance, the burner is equipped of
a combustion head with a variable geometry. Before the burner
start-up, it is recommended to choose the adjustment of the com-
bustion head according to the maximum output which the burner
will have to produce.
The hole is chosen based on the maximum output request, as
shown in Tab. I.
The factory regulation setting is preset to maximum stroke
(hole 10, Fig. 17).
Coupling position
1
2
3
4
5
6
7
8
9
10
5
4
2
1
3
20156088
Output (kW)
From
To
2600
3700
3700
4500
4500
5800
5800
8300
8300
10400
10400
12200
12200
13300
13300
14100
14100
15200
15200
16000
Installation
 remove the cover 4);
 disconnect the internal tie-rod 10);
 disconnect the electrode cable 6) from the pilot.
 disconnect the pilot 7) loosening the nut 8);
 remove the fastening screws of the head 9) and extract it.
9
D8293
Tab. I
17
GB
6
7
8
10
Fig. 16
Fig. 17
20155221

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

20154863

Table of Contents