4.11
Nozzle installation
The burner complies with the emission requirements of the
EN 267 standard. In order to guarantee that emissions do not
vary, recommended and/or alternative nozzles specified by Riello
in the Instruction and warning booklet should be used.
It is advisable to replace the nozzle once a year
during periodical maintenance.
WARNING
The use of nozzles other than those specified by
Riello S.p.A. and inadequate regular maintenance
may result into emission limits non-conforming to
the values set forth by the regulations in force, and
in extremely serious cases, into potential hazards
to people and objects.
CAUTION
The manufacturing company shall not be liable for
any such damage arising from non-observance of
the requirements contained in this manual.
Fit the nozzle with the 41 mm wrench.
To calibrate the flow rate in the nozzle, adjust the combustion
pressure on the nozzle return flow as shown in graphic in Fig. 19.
Do not use any sealing products such as gas-
kets, sealing compound, or tape.
Be careful to avoid damaging the nozzle seal-
WARNING
ing seat.
The nozzle must be screwed into place tightly
but not to the maximum torque value pro-
vided by the wrench.
4.12
Mechanical atomization lance
For the replacement of the sealing rings 1) 2) 3) and 4)(Fig. 20)
we recommend the purchase of the O-Ring kit code 20019166.
The pneumatic actuation valve of the lance operates with com-
pressed air at a pressure of 5 ÷ 7 bar.
4.13
Positioning the pilot electrode
Position the electrode as shown in Fig. 21.
WARNING
20155221
Installation
4.11.1 Recommended nozzles
Bergonzo CT5 45° (300 - 1700 kg/h)
To replace the seals, the purchase of O-Ring kit code 20019166
is recommended.
1200
1000
800
600
400
200
0
0
ARIA/AIR
4
D3899
18
GB
D8544
5
10
15
20
Return line pressure - bar
1
2
3
5
Fig. 18
D8566
25
30
Fig. 19
D9926
Fig. 20