4.7

Access to head internal part

The burner leaves the factory set for opening to the right, there-
fore maintaining the pin 1)(Fig. 16) in the housing.
To open the burner towards the right, proceed as follows:
A
disconnect the plug/socket 6)(Fig. 16) of the maximum gas
pressure switch;
B
remove the screws 2);
C
open the burner to a maximum of 100-150 mm by rotating
around the hinge and release the cables of electrodes and
the ionisation probe 5);
D
fully open the burner as in Fig. 16;
E
undo the screw 4) with pressure test point;
F
release the combustion head by lifting it from its housing 3),
then take out the combustion head.
To open the burner from the opposite side, before
removing the pin 1)(Fig. 16), make sure that the 4
screws 2) are tight.
WARNING
Then shift the pin 1) to the opposite side and then
proceed as described above at point A).
4.8

Ionization probe and electrodes position

Check that the ionization probe and electrodes
are placed as in Fig. 17, according to the dimen-
sions indicated.
WARNING
20205048
Installation
6
4 ± 0.5
22
GB
2 4
2
1
7
5
1
2
3
20198256
Fig. 16
20188099
13
± 1
31
±1
Fig. 17