Light Oil Supply; General Supply Layout (Example) - Riello DB16 LSM C13 Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burner, two stage progressive or modulating operation
Table of Contents

Advertisement

Available languages

Available languages

4.14

Light oil supply

Explosion danger due to fuel leaks in the pres-
ence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure the fuel interception tap is closed be-
fore performing any operation on the burner.

4.14.1 General supply layout (example)

An example of the burner's hydraulic diagram is shown in Fig. 22.
Key (Fig. 22)
AD
Air damper
BP
Pilot burner
C
Anti-vibration joint
CL
Oil collector
Cm
Regulating cam
GF
Gas filter
HPG
High gas pressure regulator
LPG
Low gas pressure regulator
MM
Pressure gauge
MN
Oil delivery pressure gauge
MR
Oil return pressure gauge
N
Nozzle
NL
Oil lance
PA
Minimum air pressure switch
PCV
Gas pressure regulator
PGM
Maximum gas pressure switch
PGm
Minimum gas pressure switch
POM
Maximum oil pressure switch
POm
Minimum oil pressure switch
RG
Gas butterfly valve
RP
Oil return pressure regulator
Installation
WARNING
20130281
SM
Servomotor
SRV
Pressure limiting valve with outlet into the environment
VE
Fan
VP
Pilot solenoid valves
VPS
Leak detection control device
VR
Gas pressure regulator solenoid valve
VR1-2 Oil safety valve on return
VS
Gas safety solenoid valve
VS1-2 Oil safety valve
VU
Nozzle valve
19
GB
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
Fig. 22
20155221

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

20154863

Table of Contents