EMC and leakage currents
3.1.3

Power supply harmonics

The inverter may generate power supply harmonics from its converter circuit to affect the power generator, power capacitor
etc. Power supply harmonics are different from noise and leakage currents in source, frequency band and transmission path.
Take the following countermeasure suppression techniques.
The differences between harmonics and RF noises are indicated below:
Item
Frequency
Environment
Quantitative understanding
Generated amount
Affected equipment immunity
Suppression example
Suppression technique
The harmonic current generated from the inverter
to the input side differs according to various
conditions such as the wiring impedance, whether
a reactor is used or not, and output frequency and
output current on the load side.
For the output frequency and output current, we
understand that this should be calculated in the
conditions under the rated load at the maximum
operating frequency.
NOTE
The power factor improving capacitor and surge suppressor on the inverter output side may be overheated or damaged
by the harmonic components of the inverter output. Also, since an excessive current flows in the inverter to activate
overcurrent protection, do not provide a capacitor and surge suppressor on the inverter output side when the motor is
driven by the inverter. For power factor improvement, install a reactor on the inverter input side or in the DC circuit.
44
Harmonics
Normally 40th to 50th degrees or less
(up to 3kHz or less)
To-electric channel, power impedance
Theoretical calculation possible
Nearly proportional to load capacity
Specified in standard per equipment
Provide reactor.
Power
supply
High frequency (several 10kHz to 1GHz order)
To-space, distance, wiring path
Random occurrence, quantitative grasping difficult
Change with current variation ratio (larger as switching
speed increases)
Different depending on manufacturer's equipment
specifications
Increase distance.
MCCB
MC
R
X
S
Y
T
Z
AC reactor
(FR-HAL)
Noise
DC reactor
(FR-HEL)
P/+
P1
R/L1
U
S/L2
V
T/L3
W
Inverter
Do not insert
power factor improving
capacitor.
IM