Special operation and frequency control
(5) PID automatic switchover control (Pr. 127)
The system can be started up without PID control only at a start.
When the frequency is set to Pr. 127 PID control automatic switchover frequency within the range 0 to 400Hz, the inverter
starts up without PID control from a start until output frequency is reached to the set frequency of Pr. 127, and then it shifts
to PID control. Once the system has entered PID control operation, it continues PID control even if the output frequency
falls to or below Pr.127.
Output frequency
Pr. 127
STF
PID
(6) PID output suspension function (SLEEP function) (SLEEP signal, Pr. 575 to Pr. 577 )
The inverter stops operation if the output frequency after PID operation remains at less than the Pr. 576 Output interruption
detection level setting for longer than the time set in Pr. 575 Output interruption detection time. This function can reduce
energy consumption in the low-efficiency, low-speed range.
When the deviation (= set value - measured value) reaches the PID output shutoff cancel level (Pr. 577 setting -1000%)
while the PID output interruption function is ON, the PID output interruption function is canceled and PID control operation
is resumed automatically.
While the PID output interruption function is ON, the PID output interruption signal (SLEEP) is output. At this time, the
inverter running signal (RUN) is OFF, and the PID control operating signal (PID) is ON.
For the terminal used for the SLEEP signal output, assign the function by setting "70" (positive logic) or "170" (negative
logic) in Pr. 190, Pr. 192 or Pr. 197 (output terminal function selection).
Reverse action (Pr.128
Deviation
Pr.577 - 1000%
Output frequency
Pr.576
RUN
PID
SLEEP
(7) PID monitor function
The PID control set point, measured value and deviation value can be displayed on the operation panel and output from
terminal FM.
Integral value indicating a negative % can be displayed on the deviation monitor. 0% is displayed as 1000. (The deviation
monitor cannot be output from the terminal FM.)
For each monitor, set the following value in Pr. 52 DU/PU main display data selection and Pr. 54 FM terminal function selection.
Setting
Monitor Description
52
PID set point
53
PID measured value
54
PID deviation
218
Without
PID control
PID control
10)
Less than Pr. 575
Pr. 575 or more SLEEP period
Minimum
Increments
0.1%
0.1%
0.1%
OFF
ON
Terminal FM
Full Scale
100%
100%
Value cannot be set to Pr. 54.
Displays 1000 when the PID deviation is 0%.
Time
Cancel
level
Time
Remarks