Monitor display and monitor output signal
Types of Monitor
Unit
Converter output
0.1V
voltage
Regenerative brake
0.1%
duty
Electronic thermal
relay function load
0.1%
factor
Output current peak
0.01A
value
Converter output
0.1V
voltage peak value
Output power 
0.01kW
Input terminal status
Output terminal
status
Cumulative
1h
energization time 
Reference voltage
output
Actual operation time
1h
, 
Motor load factor
0.1%
Cumulative power  0.01kWh 
PID set point
0.1%
PID measured value
0.1%
PID deviation
0.1%
Inverter I/O terminal
monitor
Motor thermal load
0.1%
factor
Inverter thermal load
0.1%
factor
132
Pr. 52 Setting
Operation
PU
Pr. 54 (FM)
panel
main
Setting
LED
monitor

8

9

10

11

12

14


20
23
24
25
52
53
54
55
61
62
Terminal FM
Full Scale Value
100V class,
400V
8
200V class
400V class 800V
9
Pr. 70
10
100%
11
Pr. 56
100V class,
400V Holds and displays the peak value of the
200V class
12
400V class 800V
Rated inverter
14
power  2
21
24
200%
52
100%
53
100%
Thermal relay
61
operation level
(100%)
Thermal relay
62
operation level
(100%)
Description
Displays the DC bus voltage value.
Brake duty set in Pr. 30, Pr. 70
Displays the thermal cumulative value on
the assumption that the thermal operation
level is 100% (Larger thermal between the
motor thermal and transistor thermal). 
Holds and displays the peak value of the
output power monitor.
(Cleared at every start)
DC bus voltage value.
(Cleared at every start)
Displays the power on the inverter output
side
Displays the input terminal ON/OFF status
on the operation panel.
(Refer to page 134.)
Displays the output terminal ON/OFF
status on the operation panel.
(Refer to page 134.)
Adds up and displays the energization time
after inverter shipment.
You can check the numbers of the monitor
value exceeded 65535h with Pr. 563.
Terminal FM:
Output 1440 pulse/s
Adds up and displays the inverter operation
time.
You can check the numbers of the monitor
value exceeded 65535h with Pr. 564.
Can be cleared by Pr. 171. (Refer to page
135.)
Displays the output current value on the
assumption that the inverter rated current
value is 100%.
Monitor value = output power monitor value
/ inverter rated current 100 [%]
Adds up and displays the power amount
based on the output power monitor.
Can be cleared by Pr. 170. (Refer to page
134.)
Displays the set point, measured value and
deviation during PID control (Refer to page
218 for details.)
Displays the ON/OFF status of the inverter
input terminal and output terminal on the
operation panel (Refer to page 134 for
details.)
Motor thermal heat cumulative value is
displayed.
(Motor overload trip (E.THM) at 100%)
Transistor thermal heat cumulative value is
displayed.
(Inverter overload trip (E.THT) at 100%)