EMC and leakage currents

3.1
EMC and leakage currents
3.1.1

Leakage currents and countermeasures

Capacitances exist between the inverter I/O cables, other cables and earth and in the motor, through which a leakage current
flows. Since its value depends on the static capacitances, carrier frequency, etc., low acoustic noise operation at the
increased carrier frequency of the inverter will increase the leakage current. Therefore, take the following measures. Select
the earth leakage current breaker according to its rated sensitivity current, independently of the carrier frequency setting.
(1) To-earth (ground) leakage currents
Leakage currents may flow not only into the inverter's own line but also into the other lines through the earth (ground) cable,
etc. These leakage currents may operate earth (ground) leakage circuit breakers and earth leakage relays unnecessarily.
Suppression technique
 If the carrier frequency setting is high, decrease the Pr. 72 PWM frequency selection setting.
Note that motor noise increases. Selecting Pr. 240 Soft-PWM operation selection makes the sound inoffensive.
 By using earth leakage circuit breakers designed for harmonic and surge suppression in the inverter's own line and other
line, operation can be performed with the carrier frequency kept high (with low noise).
To-earth (ground) leakage currents
 Take caution as long wiring will increase the leakage current. Decreasing the carrier frequency of the inverter reduces the
leakage current.
 Increasing the motor capacity increases the leakage current. The leakage current of the 400V class is larger than that of
the 200V class.
(2) Line-to-line leakage currents
Harmonics of leakage currents flowing in static capacitances between the inverter output cables may operate the external
thermal relay unnecessarily. When the wiring length is long (50m or more) for the 400V class small-capacity model (7.5kW or
lower), the external thermal relay is likely to operate unnecessarily because the ratio of the leakage current to the rated motor
current increases.
Line-to-line leakage current data example (400V class)
Motor Capacity
Rated Motor
(kW)
Current (A)
0.4
1.1
0.75
1.9
1.5
3.5
2.2
4.1
3.7
6.4
5.5
9.7
7.5
12.8
Measures
 Use Pr. 9 Electronic thermal O/L relay.
 If the carrier frequency setting is high, decrease the Pr. 72 PWM frequency selection setting.
Note that motor noise increases. Selecting Pr. 240 Soft-PWM operation selection makes the sound inoffensive.
To ensure that the motor is protected against line-to-line leakage currents, it is recommended to use a temperature
sensor to directly detect motor temperature.
Installation and selection of molded case circuit breaker
Install a molded case circuit breaker (MCCB) on the power receiving side to protect the wiring of the inverter input side.
Select the MCCB according to the inverter input side power factor (which depends on the power supply voltage, output
frequency and load). Especially for a completely electromagnetic MCCB, one of a slightly large capacity must be selected
since its operation characteristic varies with harmonic currents. (Check it in the data of the corresponding breaker.) As an
earth leakage current breaker, use the Mitsubishi Electric earth leakage current breaker designed for harmonics and surge
suppression.
40
Leakage Current (mA) *
Wiring length 50m
620
680
740
800
880
980
1070
*The leakage current of the 200V class is about a half.
MCCB
MC
Power
supply
Line-to-line leakage currents path
Wiring length 100m
1000
1060
1120
1180
1260
1360
1450
Thermal relay
Inverter
Line-to-line static
capacitances
Motor: SF-JR 4P
Carrier frequency: 14.5kHz
2
Used wire: 2mm
, 4 cores
Cabtyre cable
Motor
IM