Mitsubishi Electric FR-D720 K Series Instruction Manual page 194

Table of Contents

Advertisement

Communication operation and setting
(3) Communication operation presence/absence and data format types
Data communication between the computer and inverter is made in ASCII code (hexadecimal code).
Communication operation presence/absence and data format types are as follows:
No.
Operation
Communication request is sent to the
1)
inverter in accordance with the user
program in the computer.
2)
Inverter data processing time
Reply data from the
3)
inverter (Data 1) is
checked for error)
4)
Computer processing delay time
Answer from
computer in response
5)
to reply data 3).
(Data 3) is checked
for error)

In the communication request data from the computer to the inverter, 10ms or more is also required after "no data error (ACK)". (Refer to page 192.)

Reply from the inverter to the inverter reset request can be selected. (Refer to page 196.)

When any of "0.01 to 9998" is set in Pr. 37 and "01" in instruction code, HFF sets data format to A2 or E2. In addition, data format is always A2 and E2
for read or write of Pr. 37.

At mode error, and data range error, C1 data contains an error code. (Refer to page 200.) Except for those errors, the error is returned with data format
D.
Data writing format
Communication request data from the computer to the inverter 1)
Format
1
2
3
Inverter
ENQ
A
station


number
Inverter
ENQ
station
A1


number
Inverter
ENQ
A2
station


number
Inverter
ENQ
A3
station


number
Reply data from the inverter to the computer 3) (No data error detected)
Format
1
2
3
Inverter
ACK
C
station


number
Inverter
STX
station
C1


number
Reply data from the inverter to the computer 3) (With data error)
Number of Characters
Format
1
2
3
Inverter
NAK
D
station


number

Indicate a control code

Specify the inverter station numbers between H00 and H1F (stations 0 to 31) in hexadecimal.

Set waiting time. When the Pr. 123 PU communication waiting time setting is other than "9999", create the communication request data without "waiting time"
in the data format. (The number of characters decreases by 1.)

CR, LF code
When data is transmitted from the computer to the inverter, codes CR (carriage return) and LF (line feed) are automatically set at the end of a data group
on some computers. In this case, setting must also be made on the inverter according to the computer. Whether the CR and LF codes will be present or
absent can be selected using Pr. 124 PU communication CR/LF selection.
190
Run
Command
A1
Present
No error
C
(Request
accepted)
With error
(Request
D
rejected)
No error
Absent
(No inverter
processing)
With error
(Inverter outputs
Absent
3) again.)
4
5
6
7
8
Instruction

code
Instruction

Data
code
Instruction

code
Send
Receive
Instruction

data
data
code
type
type
4
5
6
7
8

Send
Receive
Error
Error
data
data
code 1
code 2
type
type
4
5
Error

code
Operation
Multi
Parameter
Frequency
command
Write
A3
A, A2
A, A2
Present
Present
Present
C
C1
D
D
10ms or more
Absent
Absent
Absent
(C)
Absent
F
Absent
Number of Characters
9
10
11
12
Sum
Data
check
Sum

check
Data
Data1
Number of Characters
9
10
11
12
Data1
Inverter
Monitor
Reset
A
B
Present
Present
E, E1, E2,
C
C
E3
D
D
D
Absent
Absent
(C)
Absent
F
13
14
15
16
17

Sum

check
Data2
13
14
15
16
17
ETX
Data2

Parameter
Read
B
Present
E, E2
D
Absent (C)
F
18
19
Sum

check
18
19
Sum

check

Advertisement

Table of Contents
loading

Table of Contents