Rotate housing

To improve field access to wiring or to better view the optional LCD
display:
Procedure
1. Loosen the housing rotation set screw using a 5/64 -in. hex
wrench.
Figure 5-1: Housing rotation
2. Rotate the housing clockwise to the desired location.
3. If the desired location cannot be achieved due to thread
limitation, rotate the housing counterclockwise to the desired
location (up to 360° from thread limit).
4. Retighten the housing rotation set screw to no more than 7
in.-lbs. when desired location is reached.
Quick Start Guide
A
A. Housing rotation set screw (5/64-in.)
Quick Start Guide