Emerson Rosemount 2051 Series Quick Start Manual page 25

Pressure transmitter and flow meter
Hide thumbs Also See for Rosemount 2051 Series:
Table of Contents

Advertisement

September 2023
5. Change damping.
6. Configure LCD display (if installed).
7. Review transmitter configuration and place in service.
Quick Start Guide
To use guided setup:
a. Navigate to Configure → Guided Setup and select
Change Damping.
Note
Guided setup will automatically go through each
step in the proper order.
b. Enter the desired damping value in seconds. The
permitted range of values is 0.4 to 60 seconds.
To use manual setup:
a. Navigate to Configure → Manual Setup → Process
Variable and select Change Damping.
b. Enter the desired damping value in seconds. The
permitted range of values is 0.4 to 60 seconds.
To use guided setup:
a. Navigate to Configure → Guided Setup and select
Local Display Setup.
Note
Guided setup will automatically go through each
step in the proper order.
b. Check the box next to each parameter to be
displayed to a maximum of four parameters. The
LCD display will continuously scroll through the
selected parameters.
To use manual setup:
a. Navigate to Configure → Manual Setup and select
Local Display Setup.
b. Check each parameter to be displayed. The LCD
display will continuously scroll through the selected
parameters.
a) To review the transmitter configuration, navigate using
the guided setup navigation sequences for AI Block Unit
Setup, Change Damping, and Set up LCD Display.
b) Change any values as necessary.
c) Return to the Overview screen.
Quick Start Guide
25