Set the switches

Set simulate and security switch configuration before installation as
shown in
The simulate switch enables or disables simulated alerts and
simulated AI Block status and values. The default simulate switch
position is enabled.
The security switch allows (unlocked symbol) or prevents (locked
symbol) any configuration of the transmitter.
Default security is off (unlocked symbol).
You can enable or disable the security switch in the software.
Use the following procedure to change the switch configuration:
Procedure
1. If the transmitter is installed, secure the loop, and remove
power.
2. Remove the housing cover opposite the field terminal side.
Do not remove the instrument cover in explosive atmospheres
when the circuit is live.
3. Slide the security and simulate switches into the preferred
position.
4. Replace the housing cover.
NOTICE
Emerson recommends tightening the cover until there is no
gap between the cover and housing.