Figure 2-1 – Transmitter Installation
Examples (liquid, gas or steam)
Please note that transmitters depicted in Figure 2-1 are intended for reference only.

Conduit Connections

Electronics Housing

Installation
The conduit connections to the transmitter are threaded.
Options available are 1/2-14 NPT, M20 x 1.5, and PG 13.5.
Two conduits are available on the transmitter housings for
convenient installation. Close off the unused conduit with the
compatible thread type stainless steel plug provide with the
transmitter. Use your plant-approved thread sealant on the
conduit connection threads and install the plug per the torque
values in Table 5-2 in Section 5: Maintenance and
Troubleshooting.
NOTE
A Swagelok
rotatable two-piece 90 degree elbow is available.
®
Please contact Rosemount Nuclear for ordering information.
The standard transmitter orientation is shown in dimensional
drawings found in this manual (see Figure 2-5). Use the
following procedure to rotate the electronics housing for
improved field access to wiring or the zero/span screws:
1. Loosen the housing rotation set screws.
2. First rotate the housing clockwise to the desired
location. If the desired location cannot be achieved
due to thread limit, rotate the housing counter
clockwise to the desired location (up to 360° from
thread limit).
3. Retighten the housing rotation set screws.
Rosemount 2151N