5 ACTUAL VALUES
S LAST TRIP DATA
S [ENTER] for more
GE Power Management
ð
CAUSE OF LAST TRIP:
ENTER
No Trip to Date
ESCAPE
TIME OF LAST TRIP:
ESCAPE
09:00:00.00
MESSAGE
DATE OF LAST TRIP:
ESCAPE
Jan 01 1995
MESSAGE
MOTOR SPEED DURING
ESCAPE
TRIP: Low Speed
MESSAGE
TACHOMETER
ESCAPE
PRETRIP: 3600 RPM
MESSAGE
A:
0 B:
ESCAPE
C:
0 A PreTrip
MESSAGE
MOTOR LOAD:
ESCAPE
0.00 x FLA PreTrip
MESSAGE
CURRENT UNBALANCE
ESCAPE
PRETRIP: 0%
MESSAGE
GROUND CURRENT
ESCAPE
PRETRIP: 0.00 Amps
MESSAGE
A:
0 B:
ESCAPE
C:
0 A Diff.PreTrip
MESSAGE
HOTTEST STATOR RTD
ESCAPE
RTD #1: 0°C PreTrip
MESSAGE
HOTTEST STATOR RTD
ESCAPE
RTD #7: 0°C PreTrip
MESSAGE
HOTTEST STATOR RTD
ESCAPE
RTD #11: 0°C PreTrip
MESSAGE
AMBIENT RTD
ESCAPE
RTD#12: 0°C PreTrip
MESSAGE
Vab:
0 Vbc:
0
ESCAPE
Vca:
0 V PreTrip
MESSAGE
Van:
0 Vbn:
0
ESCAPE
Vcn:
0 V PreTrip
MESSAGE
PRETRIP SYSTEM
ESCAPE
FREQUENCY: 0.00 Hz
MESSAGE
469 Motor Management Relay
Range: No Trip to Date, Incomplete Sequence, Remote Trip,
Speed Switch, Load Shed, Pressure Switch, Vibration
Switch,
General
Mechanical Jam, Undercurrent, Current Unbalance,
Ground
Fault,
Tachometer, RTDs 1-12, Undercurrent, Overvoltage,
Phase Reversal, Frequency, Reactive Power, Power
Factor, Underpower, Analog Inputs 1-4
Range: hour:min:sec
Range: Month Day Year
Range: High Speed, Low Speed
Message seen only if Two-Speed Motor is enabled
Range: 0 to 3600 RPM. Seen only if one of the Assignable
Digital Inputs is programmed as Tachometer.
Range: 0 to 100000 A
0
Range: 0.00 to 20.00 x FLA
Range: 0 to 100%
Range: 0.0 to 5000.0 A
Range: 0 to 5000 A
0
Message not seen if Differential CT programmed as None
Range: –50 to 250°C
Seen only if at least 1 RTD programmed as Stator
Range: –50 to 250°C
Seen only if at least 1 RTD programmed as Bearing
Range: –50 to 250°C
Seen only if at least 1 RTD programmed as Other
Range: –50 to 250°C
Seen only if at least 1 RTD programmed as Ambient
Range: 0 to 20000 V
Not seen if VT Connection is programmed as None
Range: 0 to 20000 V
Not seen if VT Connection is programmed as Wye
Range: 0.00, 20.00 to 120.00 Hz
Not seen if VT Connection is programmed as None
5.2 A1 STATUS

5.2.2 LAST TRIP DATA

Sw,
Overload,
Short
Circuit,
Phase
Differential,
Acceleration,
5
5-3