Advertisement

5.2 A1 STATUS
5
Any active alarms may be viewed here.
5-6
REACTIVE POWER
ESCAPE
ALARM: +2000 kvar
MESSAGE
UNDERPOWER
ESCAPE
ALARM: 200 kW
MESSAGE
TRIP COUNTER
ESCAPE
ALARM: 25 Trips
MESSAGE
STARTER FAILURE:
ESCAPE
Trip Coil Super
MESSAGE
CURRENT DEMAND
ESCAPE
ALARM: 1053 A
MESSAGE
kW DEMAND
ESCAPE
ALARM: 505 kW
MESSAGE
kvar DEMAND
ESCAPE
ALARM: –2000 kvar
MESSAGE
kVA DEMAND
ESCAPE
ALARM: 2062 kVA
MESSAGE
ANALOG I/P 1
ESCAPE
ALARM: 201 Units
MESSAGE
EMERGENCY RESTART:
ESCAPE
Trip Still Present
MESSAGE
ALARM, 469 NOT
ESCAPE
INSERTED PROPERLY
MESSAGE
469 NOT IN SERVICE
ESCAPE
Simulation Mode
MESSAGE
RTD #1
ESCAPE
HI ALARM:
135°C
MESSAGE
ANALOG 1-2
ESCAPE
ALARM:
50%
MESSAGE
ANALOG 3-4
ESCAPE
ALARM:
50%
MESSAGE
469 Motor Management Relay
Range: –50000 to +50000 kvar
Current kvar value is shown here
Range: –50000 to +50000 kW
Current kW value is shown here
Range: 1 to 10000 Trips
Total number of motor trips is displayed here
Range: Trip Coil Super, Welded Contactor, Breaker Failure
The type of failure is displayed here
Range: 1 to 10000 A
The current Running Current Demand is shown here
Range: –50000 to +50000 kW
Current Running kW Demand is shown here
Range: –50000 to +50000 kvar
Current Running kvar Demand is shown here
Range: 0 to 50000 kVA
Current Running kVA Demand is shown here
Range: –50000 to +50000. Reflects the Analog Input Name as
programmed. The Analog Input level is shown here.
Range: Trip Still Present, Block Still Present,
No Trips & No Blocks
If the 469 chassis is only partially engaged with the case, this
service alarm appears after 1 sec. Secure the chassis handle to
ensure that all contacts mate properly
Range: Not Programmed, Simulation Mode, Output Relays
Forced, Analog Output Forced, Test Switch Shorted
Range: 1 to 250°C. Similar Hi Alarms will occur for other RTDs.
The message reflects the Alarm Name as programmed
Range: 0 to 999 (% Diff) or 0 to 99999 (Abs Diff)
The alarm message reflects the Alarm Name as programmed
Range: 0 to 999 (% Diff) or 0 to 99999 (Abs Diff)
The alarm message reflects the Alarm Name as programmed
5 ACTUAL VALUES