5.6 A5 EVENT RECORDER
The event recorder stores motor and system information each time an event occurs. An event description is
stored along with a time and date stamp for troubleshooting purposes. Events include all trips, any alarm
optionally (except Service Alarm, and 469 Not Inserted Alarm, which always records as events), loss of control
power, application of control power, emergency restarts, and motor starts when a blocking function is active.
The latter event could occur if the block start contacts were shorted out to bypass the 469 and start the motor.
EVENT 01 is the most recent event and EVENT 40 is the oldest event. Each new event bumps the other event
records up one until EVENT 40 is reached. The event record in EVENT 40 is lost when a new event occurs. This
information can be cleared using the S1 469 SETUP \ CLEAR DATA \ CLEAR EVENT RECORD setpoint.
5
5-24
ANALOG I/P 1
ESCAPE
EVENT01: 0 Units
MESSAGE
ANALOG I/P 2
ESCAPE
EVENT01: 0 Units
MESSAGE
ANALOG I/P 3
ESCAPE
EVENT01: 0 Units
MESSAGE
ANALOG I/P 4
ESCAPE
EVENT01: 0 Units
MESSAGE
469 Motor Management Relay
Range: –50000 to 50000
Range: –50000 to 50000
Range: –50000 to 50000
Range: –50000 to 50000
5 ACTUAL VALUES