Analog Inputs 1-4 - GE 469 Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

4 SETPOINT PROGRAMMING
S ANALOG INPUT 1
S [ENTER] for more
GE Power Management
ð
ANALOG INPUT 1:
ENTER
Disabled
ESCAPE
ANALOG INPUT 1 NAME:
ESCAPE
Analog I/P 1
MESSAGE
ANALOG INPUT 1 UNITS:
ESCAPE
Units
MESSAGE
ANALOG INPUT 1
ESCAPE
MINIMUM: 0
MESSAGE
ANALOG INPUT 1
ESCAPE
MAXIMUM: 100
MESSAGE
ANALOG INPUT 1 BLOCK
ESCAPE
FROM START: 0 s
MESSAGE
ANALOG INPUT 1
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
ANALOG INPUT 1 ALARM
ESCAPE
LEVEL: 10 Units
MESSAGE
ANALOG INPUT 1 ALARM
ESCAPE
PICKUP: Over
MESSAGE
ANALOG INPUT 1 ALARM
ESCAPE
DELAY: 0.1 s
MESSAGE
ANALOG INPUT 1 ALARM
ESCAPE
EVENTS: Off
MESSAGE
ANALOG INPUT 1
ESCAPE
TRIP: Off
MESSAGE
ASSIGN TRIP RELAYS:
ESCAPE
Trip
MESSAGE
ANALOG INPUT 1 TRIP
ESCAPE
LEVEL: 20 Units
MESSAGE
ANALOG INPUT 1 TRIP
ESCAPE
PICKUP: Over
MESSAGE
ANALOG INPUT 1 TRIP
ESCAPE
DELAY: 0.1 s
MESSAGE
469 Motor Management Relay

4.13.2 ANALOG INPUTS 1-4

Range: Disabled, 4-20 mA, 0-20 mA, 0-1 mA
Range: 12 alphanumeric characters
Range: 6 alphanumeric characters
Range: –50000 to 50000, step 1
Range: –50000 to 50000, step 1
Range: 0 to 5000 sec., step 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
Range: –50000 to 50000, step 1
Units will reflect Analog Input 1 Units as entered above
Range: Over, Under
Range: 0.1 to 300.0 sec., step 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3
Trip & Auxiliary3
Range: –50000 to 50000; Step: 1
Units will reflect Analog Input 1 Units as entered above
Range: Over, Under
Range: 0.1 to 300.0 sec., step 0.1
4.13 S12 ANALOG I/O