Analog Output Table - GE 469 Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

4.13 S12 ANALOG I/O
c) ANALOG OUTPUT TABLE
Table 4–3: ANALOG OUTPUT PARAMETER SELECTION TABLE
PARAMETER NAME
Phase A Current
Phase B Current
Phase C Current
Avg. Phase Current
AB Line Voltage
BC Line Voltage
CA Line Voltage
Avg. Line Voltage
Phase AN Voltage
4
Phase BN Voltage
Phase CN Voltage
Avg. Phase Voltage
Hottest Stator RTD
Hottest Bearing RTD
Ambient RTD
RTD #1 to 12
Power Factor
Reactive Power
Real Power
Apparent Power
Thermal Capacity Used
Relay Lockout Time
Current Demand
kvar Demand
kW Demand
kVA Demand
Motor Load
Analog Inputs 1-4
Tachometer
MWhrs
Analog In Diff 1-2
Analog In Diff 3-4
Torque
4-78
RANGE / UNITS
0 to 100000 A
0 to 100000 A
0 to 100000 A
0 to 100000 A
50 to 20000 V
50 to 20000 V
50 to 20000 V
50 to 20000 V
50 to 20000 V
50 to 20000 V
50 to 20000 V
50 to 20000 V
–50 to +250°C or –58 to +482°F
–50 to +250°C or –58 to +482°F
–50 to +250°C or –58 to +482°F
–50 to +250°C or –58 to +482°F
0.01 to 1.00 lead/lag
-50000 to 50000 kvar
-50000 to 50000 kW
0 to 50000 kVA
0 to 100%
0 to 500 min.
0 to 100000 A
0 to 50000 kvar
0 to 50000 kW
0 to 50000 kVA
0.00 to 20.00 x FLA
–50000 to +50000
100 to 7200 RPM
0.000 to 999999.999 MWhrs
–50000 to +50000
–50000 to +50000
0 to 999999.9
469 Motor Management Relay
4 SETPOINT PROGRAMMING
STEP
DEFAULT
MIN.
MAX
1
0
100
1
0
100
1
0
100
1
0
100
1
3200
4500
1
3200
4500
1
3200
4500
1
3200
4500
1
1900
2500
1
1900
2500
1
1900
2500
1
1900
2500
1
0
200
1
0
200
1
-50
60
1
-50
250
0.01
0.8 lag
0.8 lead
1
0
750
1
0
1000
1
0
1250
1
0
100
1
0
150
1
0
700
1
0
1000
1
0
1250
1
0
1500
0.01
0.00
1.25
1
0
+50000
1
3500
3700
0.001
50.000
100.000
1
0
100
1
0
100
0.1
0
100
GE Power Management

Advertisement

Table of Contents
loading