4.13 S12 ANALOG I/O
S ANALOG IN DIFF 3-4
S [ENTER] for more
4
This feature compares two of the analog inputs and activate alarms or trips based on the difference between
them. The difference can be of an absolute difference in units or a percentage difference. The second analog
input (4 for 3-4) is used as the reference value for percentage calculations. The comparison logic can also be
selected as one input greater than the other ("3>4") or vice versa ("4>3") or as absolute difference ("3<>4").
Note that the compared analog inputs must be programmed with the same unit type prior to using this feature.
4-82
ð

ANALOG IN DIFF 3-4:

ENTER
Disabled
ESCAPE
ANALOG IN DIFF 3-4
ESCAPE
NAME: Analog 3-4
MESSAGE
ANALOG IN DIFF 3-4
ESCAPE
COMPARISON: % Diff
MESSAGE
ANALOG IN DIFF 3-4
ESCAPE
LOGIC: 3<>4
MESSAGE
ANALOG IN DIFF 3-4
ESCAPE
ACTIVE: Always
MESSAGE
A/I DIFF 1-2 BLOCK
ESCAPE
FROM START: 0 s
MESSAGE
ANALOG IN DIFF 3-4
ESCAPE
ALARM: Off
MESSAGE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
ANALOG IN DIFF 3-4
ESCAPE
ALARM LEVEL: 10%
MESSAGE
A/I DIFF 1-2 ALARM
ESCAPE
LEVEL: 10 Units
MESSAGE
ANALOG IN DIFF 3-4
ESCAPE
ALARM DELAY: 0.1 s
MESSAGE
ANALOG IN DIFF 3-4
ESCAPE
EVENTS: Off
MESSAGE
ANALOG IN DIFF 3-4
ESCAPE
TRIP: Off
MESSAGE
ASSIGN TRIP RELAYS:
ESCAPE
Trip
MESSAGE
ANALOG IN DIFF 3-4
ESCAPE
TRIP LEVEL: 10%
MESSAGE
ANALOG IN DIFF 3-4
ESCAPE
TRIP LEVEL: 10 Units
MESSAGE
ANALOG IN DIFF 3-4
ESCAPE
TRIP DELAY: 0.1 s
MESSAGE
469 Motor Management Relay
4 SETPOINT PROGRAMMING
4.13.4 ANALOG IN DIFF 3-4
Range: Disabled, Enabled
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: 12 alphanumeric characters
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: % Diff, Abs. Diff
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: 1<>2, 1>2, 2>1
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: Always, Start/Run
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: 0 to 5000 sec.; Step: 1
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: Off, Latched, Unlatched
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: 0 to 500%; Step: 1.
Seen only if Analog Inputs 1 and 2 are enabled and % Diff is Set
Range: 0 to 50000; Step: 1
Seen only if Analog Inputs 1 and 2 are enabled and Abs Diff is Set
Range: 0.1 to 300.0 sec.; Step: 0.1
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: On, Off
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: Off, Latched, Unlatched
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3
Trip & Auxiliary3
Message seen only if Analog Inputs 1 and 2 are enabled.
Range: 0 to 500%; Step: 1
Seen only if Analog Inputs 1 and 2 are enabled and % Diff is set.
Range: 0 to 50000; Step: 1
Seen only if Analog Inputs 1 and 2 are enabled and Abs Diff is Set
Range: 0.1 to 300.0 sec.; Step: 0.1
Message seen only if Analog Inputs 1 and 2 are enabled.