2.1.2 Basic 3-Wire Start, Forward and Reverse with Speed Pot Control

Speed Pot
P100 = 01 Terminal strip control
P101 = 01 0-10Vdc Speed control
P112 = 01 Forward / Reverse
P121 = 11 Start forward
P123 = 12 Start reverse can also be selected desired
P160 = Speed at minimum signal
P161 = Speed at maximum signal
3.1

PID Quick Start

3.1.1 Steps for Programming the Drive for PID

Please read the PID Parameter notes in the manual Section 4.5.4.
1. To activate PID mode, one of the TB-13x inputs (controlled with parameters 121 thru 124) must be used to select
the "Auto reference" that will become your desired set point reference. For example to have TB13A select the
keypad as the reference set P121 to 06. The setpoint reference can be anything from keypad, 0-10V, 4-20mA
or a preset speed. However, it cannot be the same source as the feed-back itself.
2. Set P200 to 1 for normal acting or 2 for reverse acting.
Normal-acting PID control will command a decrease in motor speed in response to an increasing process
variable feedback. An example of normal PID mode is a direct acting system that maintains duct pressure. Duct
pressure is the process variable that is monitored by the feedback device. As duct pressure rises, motor speed
will decrease to maintain the pressure.
Reverse acting PID control will command an increase in motor speed in response to an increasing process
variable feedback. An example of reverse PID mode is a reverse acting system that maintains water temperature
in a cooling tank. Water temperature is the process variable that is monitored by the feedback device. As
water temperature rises, motor speed needs to be increased to pump more cold water and thereby lowers the
temperature in the tank.
3. Set P201 to 0 to select the 4-20 mA feed-back source or 1 to select 0-10vdc.
4. Set P204 and P205 to transducer's minimum and maximum feedback values.
Example: Transducer rating = 0-300PSI; P204 = 0.0, P205 = 300
Lenze SMVector 13554876 EDBSV01 EN v21.0
Stop
SMV Quick Start Guide
Fwd
Start
Speed at maximum signal sets the speed the drive
will run the motor when it sees 10VDC from the pot.
Speed at minimum signal sets the speed the drive
will run the motor when it sees 0VDC from the pot.
Rev
67