4.5.3

Advanced Setup Parameters

Code
No.
Name
Analog Inputs
p156
Configuration
TB5 (0-10V) Analog
p157
Input Monitoring
Action
TB5 (0-10V) Analog
p158
Input Monitoring
Level (ML)
0-10V Analog Input
p159
Deadband
Speed at Minimum
P160
Signal
Speed at Maximum
P161
Signal
Analog Input Filter
p162
TB-25 (4-20mA)
P163
Analog Input
Monitoring Action
Lenze SMVector 13554876 EDBSV01 EN v21.0
Possible Settings
Default Selection
0
0 TB5: (0-10 VDC); TB25: (4-20mA)
1 TB5: (0 - 5 VDC); TB25: (4-20mA)
2 TB5: (2 - 10 VDC); TB25: (4-20mA)
4 TB5: (0-10 VDC); TB25: (0-20mA)
5 TB5: (0 - 5 VDC); TB25: (0-20mA)
6 TB5: (2 - 10 VDC); TB25: (0-20mA)
0
0 No Action
1 If TB5 < P158 - Trip Fault F.FAU
2 If TB5 < P158 - Run Preset #8
3 If TB5 < P158 - Run Preset Seg. #16
4 If TB5 > P158 - Trip Fault F.FAU
5 If TB5 > P158 - Run Preset #8
6 If TB5 > P158 - Run Preset Seg. #16
0.0
-10.0
{VDC}
0.0
0
{VDC}
0.0
-999.0
{Hz}
60.0
-999.0
{Hz}
NOTE
• P160 sets the output frequency at 0% analog input
• P161 sets the output frequency at 100% analog input
• P160 or P161 < 0.0 Hz: For scaling purposes only; does not indicate opposite direction!
• P160 > P161: Drive will react inversely to analog input signal
0.01
0.00
{s}
0
0 No Action
1 If TB25 < P164 - Trip Fault F.FoL
2 If TB25 < P164 - Run Preset #7
3 If TB25 < P164 - Run Preset Seg. #15
4 If TB25 > P164 - Trip Fault F.FoL
5 If TB25 > P164 - Run Preset #7
6 If TB25 > P164 - Run Preset Seg. #15
Commissioning
Selects the reaction to a loss of the 0-10V signal
at TB5
500ms is the minimum time above/below
Monitoring Level (P158) before triggering the
drive to trip or run at a preset speed.
For P157 = 3 or 6, the accel/decel time is set
in P786.
NOTE: P157 has priority over P163 and TB-13
presets/auto references (P121-P124)
10.0
Negative input voltage is not currently supported.
10.0
Not active if [-10 to +10 VDC] option is selected.
1000
P161
1000
P160
10.00
• Adjusts the filter on the analog inputs (TB-5
and TB-25) to reduce the effect of signal noise
• The P162 delay time will affect the response
time of diagnostic parameters (P520-P523).
• Selects the reaction to a loss of the 4-20 mA
signal at TB-25.
• Signal is considered lost if it falls below the
value set in P164
• Digital outputs can also indicate a loss of 4-20
mA signal; see P140, P142
• For P163 = 3 or 6, the accel/decel time is
set in P781.
NOTE: P163 has priority over TB-13 presets/auto
references (P121-P124)
IMPORTANT
f
ref
0V
10V
(4mA)
(20mA)
V0111