4.5.2

I/O Setup Parameters

Code
No.
Name
Assertion Level
p120
TB-13A Digital Input
P121
p122
TB-13B Digital Input
(Priority > TB13A)
Same as TB13A except:
3 = Preset #2
23 = Seq Seg, #2
p123
TB-13C Digital Input
(Priority > TB13B, A)
Same as TB13A except:
3 = Preset #3
23 = Seq Seg, #4
p124
TB-13D* Digital Input
(Priority > TB13C, B, A)
Same as TB13A except:
3 = Preset #4
23 = Seq Seg, #8
NOTE: P124 is
applicable to SMV
15HP (11kW) and
higher models only
WARNING
Jog overrides all STOP commands! To stop the drive while in Jog mode, the Jog input must be deactivated or a
fault condition induced.
WARNING
If the input defined to "Start Sequence" is opened during a sequence, the drive will exit sequencer mode and will run
at the specified standard or alternate speed source (dependent on drive configuration).
Lenze SMVector 13554876 EDBSV01 EN v21.0
Possible Settings
Default Selection
2
1 Low
2 High
0
0 None
1 AUTO Reference: 0-10 VDC
2 AUTO Reference: 4-20 mA
3 AUTO Reference: Preset #1
* 13D: 3 = Reserved
4 AUTO Reference: MOP Up
5 AUTO Reference: MOP Down
6 AUTO Reference: Keypad
7 AUTO Reference: Network
8 Control Select
9 Network Enable
10 Reverse Rotation
11 Start Forward
12 Start Reverse
13 Run Forward
14 Run Reverse
15 Jog Forward
16 Jog Reverse
17 Accel/Decel #2
18 DC Brake
19 Auxiliary Ramp to Stop
20 Clear Fault
21 External Fault F.EF
22 Inverse External Fault F.EF
23 AUTO Ref: Sequence Segment #1
24 Start Sequence
25 Step Sequence
26 Suspend Sequence
Commissioning
P120 and the Assertion Level switch must both
match the desired assertion level unless P100,
P121...P124 are all set to 0. Otherwise an F.AL
fault will occur.
Disables input
For frequency mode, see P160...P161,
For PID mode, see P204...P205,
For vector torque mode, see P330
For frequency mode see P131...P137,
For PID mode, see P231...P233,
For torque mode see, P331...P333
• Normally open: Close input to increase or
decrease speed, PID or torque setpoint.
• MOP Up is not active while in STOP
Use when P100 = 4, 5 to switch between terminal
strip control and local or remote keypad control.
Required to start the drive through the network.
Open = Forward
Refer to Note for typical circuit
Refer to Note for typical circuit
Jog Forward speed = P134
Jog Reverse speed = P135
Active even if P112 = 0
Refer to P125, P126
Refer to P174; close input to override P175
Normally closed: Opening input will ramp drive
to STOP according to P127, even if P111 is set
to Coast (0 or 1).
Close to reset fault
Normally closed circuit; open to trip
Normally open circuit; close to trip
Works in Speed Mode only
Transition from non-asserted to asserted state
IMPORTANT
Closed = Reverse
31