4.5.9.2

Sequencer Flow Diagram Right

1
2
3
P710
P720
P715
P712
P722
P717
SUSPEND SEQUENCE
Asserting input will suspend
sequencer in the currently active
segment, and when un-asserted
sequencer will continue to complete
the time remaining in the segment
P121/2/3/4
26
Suspend Sequencer
56
Commissioning
4
5
6
7
P730
P725
P735
P732
P737
P742
P727
Number of repeat Cycles P707
(4)
The end segment is entered once the highest number segment with a non-zero value in the
"time in current segment" (P712/P711 etc..) parameter has completed and the number of
repeat cycles P707 has completed.
> A value of "0" in the segment time (P712 etc.) will result in the segment being skipped.
> Segment time and Accel/Decel (P712/P711 etc.) scaling is seconds as default.
> The sequencer will start from the segment pointed to by the digital input with the highest priority.
> Selections shown as default values.
Action after Stop/Start (P100) transition/digital input (if setup for
sequencer mode) transition or restart after trip.
P706
Action
0
Restart at beginning of sequence (pointed by TB13x)
Restart at beginning of current segment
1
2
Start at beginning of prior segment
3
Start at beginning of next segment
8
9
10
P740
P750
P745
P755
P747
P752
P757
Ramp with DC Brake (See P174/P175)
Coast with DC Brake (See P174/P175)
Quick Stop (based on P128)
Keep running (based on P790)
Notes
Lenze SMVector 13554876 EDBSV01 EN v21.0
11
12
13
14
P760
P770
P765
P772
P762
P767
5
4
3
2
Coast to Stop
1
Stop (based on P111)
0
3
0 2
0 2
15
16
P780
P775
P785
P777
P782
P787
Number of
cycles set
No
in P707
completed
?
Yes
P790
P791
(4)
End
Segment
P792
P795