Environmental Specifications; Outputs - Emerson PACSystems RSTi User Manual

Table of Contents

Advertisement

User Manual
GFK-2745C
A-2

Environmental Specifications

A-2.1
Power Modules, Discrete Inputs, Discrete Outputs,
Analog Inputs, and Analog Outputs
Table 211: Environment Specification
Operating Temperature
Non-Operating Temperature
Relative Humidity
Operating Altitude
Mounting
Shock Operating
Shock Non-Operating
Vibration/Shock Resistance
Installation Pos. / Protect. Class
Isolation
Product Certifications and Installation Guidelines for Conformance
ST-1xxx,2xxx, 7xxx :
-20oC to 55oC for UL applications; -20oC to 60oC for non-UL
applications
ST-3xxx, 4xxx
, 51xx
, 53xx, 54xx, 56xx :
0oC to 55oC for UL applications; 0oC to 60oC for non-UL
applications
for ST-4491, ST-5101, ST-5111:
0oC to 55oC for UL applications; -20oC to 60oC for non-UL
applications
ST-52xx :
0oC to 55oC for UL applications; -20oC to 55oC for non-UL
applications
-40oC to 85oC
5% to 90% Non-condensing
2,000m
DIN Rail
10g
30g
Displacement: 0.012 Inch p-p from 10-57Hz
Acceleration: 2G's from 57-500Hz
Sweep Rate: 1 octave Per Minute
Axes to test: x, y, z
Frequency Sweeps Per Axis: 10
Variable / IP20
DC Module (Including Analog Module): Terminal Block to F.G
500Vac/1min
AC Module: Terminal Block to F.G 1500Vac/1min
Relay Module: Terminal Block to F.G 2500Vac/1min