Emerson PACSystems RSTi User Manual page 163

Table of Contents

Advertisement

User Manual
GFK-2745C
6.21.7
ST-3808
IO Input Image Data – 16 byte
Bit No
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Byte 9
Byte 10
Byte 11
Byte 12
Byte 13
Byte 14
Byte 15
-
Configuration Parameter Data – 2 byte
Byte
0
Analog Input
Bit 7
Bit 6
Ch#0 Conversion Data Low byte
Ch#0 Conversion Data High byte
Ch#1 Conversion Data Low byte
Ch#1 Conversion Data High byte
Ch#2 Conversion Data Low byte
Ch#2 Conversion Data High byte
Ch#3 Conversion Data Low byte
Ch#3 Conversion Data High byte
Ch#4 Conversion Data Low Byte
Ch#4 Conversion Data High Byte
Ch#5 Conversion Data Low Byte
Ch#5 Conversion Data High Byte
Ch#6 Conversion Data Low Byte
Ch#6 Conversion Data High Byte
Ch#7 Conversion Data Low Byte
Ch#7 Conversion Data High Byte
If the input of channel is open or over-ranged, its conversion data will be 0x8000 (-32678)
Bit 7
Bit 6
Sensor Type
Sensor Type
=00h: Type K, 0.1℃ or 0.1℉/count
=01h: Type J, 0.1℃ or 0.1℉/count
=02h: Type T, 0.1℃ or 0.1℉/count
=03h: Type B, 0.1℃ or 0.1℉/count
=04h: Type R, 0.1℃ or 0.1℉/count
=05h: Type S, 0.1℃ or 0.1℉/count
=06h: Type E, 0.1℃ or 0.1℉/count
=07h: Type N, 0.1℃ or 0.1℉/count
=08h: Type L, 0.1℃ or 0.1℉/count
=09h: Type U, 0.1℃ or 0.1℉/count
=0Ah: Type C, 0.1℃ or 0.1℉/count
=0Bh: Type D, 0.1℃ or 0.1℉/count
=80h: 10uV Input, -80.0~81.0mV, 10uV/1count
=81h: 1uV Input, -32.7~32.7mV, 1uV/1count
=82h: 2uV Input, -65.5~65.5mV, 2uV/1count
Bit 5
Bit 4
Bit 3
Bit 5
Bit 4
Bit 3
Chapter 6
Nov 2019
Bit 2
Bit 1
Bit 0
Bit 2
Bit 1
Bit 0
150

Advertisement

Table of Contents
loading

Table of Contents