PACSystems VersaMax Genius Network Interface User Manual
GFK-1535D
1.6
Genius NIU Specifications
Feature
Number of Modules
Network inputs per bus scan
Network outputs per bus scan
Discrete Input Memory
Discrete Output Memory
Analog Input Memory
Analog Output Memory
Power Consumption
Serial Bus Address
Network data rate
1.6.1
Genius NIU Compatibility
Network Interface Unit IC200GBI001 is compatible with any type of PLC
or computer capable of controlling the Genius bus. Examples:
PACSystems RX7i controller
•
PACSystems RX3i controller
•
Series 90™-70 PLC
•
Series 90™-30 PLC
•
For some products, minimum versions are required for use with a Genius
NIU:
On a Genius bus controlled by an IC697 PLC or PACSystems RX7i:
•
For a Series 90™-30 PLC
•
Introduction
IC697 CPU firmware, release 3.0 or later.
—
Genius Bus Controller release 5.4 or later. Upgrading the 90-
—
70
Genius Bus Controller firmware to version 6.0 (or higher) is
—
strongly recommended.
CPU firmware: any version.
—
Bus Controller: any version.
—
Specification
8 per rack, 64 per NIU/station
128 bytes
128 bytes
1024 points
1024 points
128 bytes
128 bytes
+5V@250mA, +3.3V@10mA
0 to 31
153.6 Kbaud extended, 153.6 Kbaud standard,
76.8 Kbaud, or 38.4 Kbaud.