Analog Output Module - Emerson PACSystems RSTi User Manual

Table of Contents

Advertisement

User Manual
GFK-2745C
10.1.5

Analog Output Module

ST-4112 (2-current analog output, 0~20mA, 12bit)
Offset
0
1
2
3
4
5
6
7
† All values are stored in Adapter's EEPROM.
Configuration Parameters and Memory Register
Valid Parameter length: 6 bytes
Parameter Data:
Decimal Bit
00-01
02-03
04-07
00-07
00-07
00-03
04-07
00-07
00-03
04-07
00-07
00-07
Description
Fault Action for channel 0
00: Fault Value, 01: Hold last state,
10: Low Limit, 11: High Limit
Fault Action for channel 1
00: Fault Value, 01: Hold last state,
10: Low Limit, 11: High Limit
Reserved
Reserved
Channel 0 Fault Value Low Byte
Channel 0 Fault Value High Byte
Reserved
Channel 1 Fault Value Low Byte
Channel 1 Fault Value High Byte
Reserved
Not used
Not used
Chapter 10
Nov 2019
Default Value
0 (Fault Value)
0 (Fault Value)
0
0
0
0
0
0
0
0
0
0
298