ST-3808 (8- Thermocouple/mV input)
Offset
0
1
2
3
4
5
6
7
† All values are stored in Adapter's EEPROM.
Configuration Parameters and Memory Register
Valid Parameter length: 4 bytes
Parameter Data:
Decimal Bit
Description
00-07
The selection Sensor Type
=00h: Type K, 0.1°C/count
=01h: Type J, 0.1°C/count
=02h: Type T, 0.1°C/count
=03h: Type B, 0.1°C/count
=04h: Type R, 0.1°C/count
=05h: Type S, 0.1°C/count
=06h: Type E, 0.1°C/count
=07h: Type N, 0.1°C/count
=08h: Type L, 0.1°C/count
=09h: Type U, 0.1°C/count
=0Ah: Type C, 0.1°C/count
=0Bh: Type D, 0.1°C/count
=80h: 10uV Input, -78.0~78.0mV, 10uV/count
=81h: 1uV Input, -32.7~32.7mV, 1uV/count
=82h: 2uV Input, -65.5~65.5mV, 2uV/count
=Others: Reserved
00
Temperature Type
0: Celsius(°C), 1: Fahrenheit(°F)
01
0: Cold Junction Compensation
1: Disable Compensation
02
Data Resolution
0: 0.1°C, °F /bit, 1: 1°C, °F /bit
03
Reserved
04
Filter Type
0: Normal Filter, 1: Enhanced Filter
05-07
Reserved
00-07
Cold Junction Temperature Offset Data Low Byte
00-07
Cold Junction Temperature Offset Data High Byte
00-07
Not used
00-07
Not used
00-07
Not used
00-07
Not used
Chapter 10
Nov 2019
Default
Value
0: Type K
0: Celsius(°C)
0
0
0: Normal Filter
0
0
0
0
0
0
0
297