10. Basic settings
Unit parameter
Unit name
Bus address
Global address
Local stop
Monitoring stop
Sequencing stop
Terminal language
Temperature unit
Temperature setpoint
Temperature setpoint, night
Humidity setpoint
Water pressure setpoint
Supply air pressure setpoint
Condensation pressure DX 1/2
Condensation pressure Mix 1/2
SAPSM time delay
Winter start time delay
Summer/winter change-over
Summer/winter hysteresis
Cooling priority
Additional capacity - Cooling
Additional capacity - Humidification
Additional capacity - Dehumidification
Integral factor
Output D-OUT common alarm
Output D-OUT Winter operation
Input D-IN remote on/off
Output D-OUT local stop
Input D-IN CW stop
Control type
Limiting control - Start temperature
Limiting control - Start temperature 2
Limiting control - Temp. increase
Min. temperature
Max. temperature
Limiting control - Start humidity
Limiting control - Humidity increase
Unit runtime
Stop time
Cooling runtime
Heating runtime
Humidification runtime
Dehumidification runtime
Free Cooling runtime
Mixed mode runtime
62
Range
16 characters
Unit name
0 - 19
0 - 32767
0 - 1
0 - 1
0 - 1
0: English
1: German
0: °C 1: °F
5 - 50 °C
5 - 50 °C
5 - 90 % r.h
45% r.h
0 - 6 bar
1.5 bar
0 - 327.67 Pa
0.00 Pa
0 - 40 bar
18/18 bar
0 - 40 bar
12/12 bar
0 - 65535 s
0 - 300 s
5 - 35 °C
1 - 9.9 K
0: GE 1: CW 2: DX
0 - 9.9 K
0 - 20 % r.h
0 % r.h
0 - 20 % r.h
0 % r.h
0 - 10 %
0 - 31
0 - 31
0 - 43
0 - 31
0 - 43
1 - 5
0 - 40 °C
0 - 40 °C
0 - 20 K
0 - 40 °C
0 - 40 °C
0 - 90 % r.h
70 % r.h
0 - 20 % r.h
0.5 % r.h
0 - 2,147,483,647*
0 - 2,147,483,647
0 - 2,147,483,647
0 - 2,147,483,647
0 - 2,147,483,647
0 - 2,147,483,647
0 - 2,147,483,647
0 - 2,147,483,647
Value
0
1
1
0
0
0
0
24°C
27 °C
0 s
180 s
16 °C
2 K
0
0.0 K
0 %
6
0
10
0
0
1
16 °C
0 °C
0.5 K
0 °C
40 °C
0 h
0 h
0 h
0 h
D-IN - Digital input
D-OUT - Digital output
0 h
A-IN - Analog input
0 h
A-OUT - Analog output
0 h
0 h
* 2
31
- 1 = 2,147,483,647
BA C7000 for EC Tower | EN | 01-2019 | 1000755