Alarm change-over
So that there is a change-over when alarms occur, alarms can be defined as
valid in menus Z3a, Z3b, Z3c and Z3d by adjusting the parameter to "1". If this
type of alarm (which is defined as valid) occurs, the defective unit is switched
off and the standby unit with the next highest bus address is switched on. If
another unit with a valid alarm in the zone fails, a further standby unit is switched
on if there is one available.
Some alarms lead to the defective unit being switched off or to certain functions
being deactivated even if the alarm has not been defined as valid (for details,
see chapter "11.4 Alarm texts" on page 72).
The "Unit not reachable" alarm cannot be left out of the configuration and so
always remains valid. This alarm also occurs if the unit is de-energized.
Valid alarms:
--.Not reachable
02.Replaced by 30, 31, 32
04.Heater error
06.Humidifier 5uS
08.Airflow failure
10.External alarm
12.Dry cooler error
14.Return air temp. too high 15.Return air humidity too high
16.Supply air temp. too high 17.Supply air humidity too high
18.Return air temp. too low
20.Supply air temp. too low
22.Replaced by 37, 38, 39
24.Fire/smoke detector
26.Sensor fracture
28.Phase failure
30.Refrigerant circuit 1
32.Refrigerant circuits 1&2
34.Reserved for CyberCool2
36.Reserved for CyberCool2
38.Water temp. in 2 high
40.Water temp. in 1 low
42.Water temp. in 1&2 low
BA C7000 for EC Tower | EN | 01-2019 | 1000755
01.Switched off manually
03.Replaced by 30, 31, 32
05.Humidifier error
07.Humidifier 20uS
09.Filter contaminated
11.Pumps error
13.Water detector
19.Return air humidity too low
21.Supply air humidity too low
23.Replaced by 40, 41, 42
25.Sensor error
27.Refrigerant heater failure
29.BMS stop 1
31.Refrigerant circuit 2
33.Reserved for CyberCool2
35.Reserved for CyberCool2
37.Water temp. in 1 high
39.Water temp. in 1 & 2 high
41.Water temp. in 2 low
Config/Zone/More/Valid alarms
(Z3a)
.../Valid alarms (Z3b)
.../Valid alarms (Z3c)
.../Valid alarms (Z3d)