4 5 4 Error messages
The boiler is equipped with a self-diagnostics system in or-
der to help the maintenance personnel identify the causes
of any anomalies.
When a technical anomaly occurs, the display on the left
will either show the letter "A" or the letter "E", while the dis-
play on the right will show a numeric error code, which will
allow the maintenance personnel to identify the possible
cause.
- If the letter "A" appears on the left-hand display, this
means that the "RESET" button will have to be pressed
after the cause of the fault has been eliminated.
- If the letter "E" appears on the left-hand display, this
means that the boiler will resume functioning normal-
ly, without having to press the "RESET" button, once
the cause of the fault has been eliminated.
The list of the error codes and the descriptions of the rela-
tive anomalies are provided below:
Error
type
A 01
No flame.
The burner turned off three times during a
request for heat.
Defective ignition transformer.
A 02
Defective ignition transformer power cord (see
fastons on the circuit board).
Flue gas pipe obstructed or partially obstruct-
ed.
The delivery temperature has exceeded the
A 03
set value.
Possible safety thermostat intervention due to
A 04
overheating.
A 05
Temporary internal fault.
Low temperature zone safety thermostat inter-
A 07 (*)
vention (if present).
The ignition relay does not work well. Press
the reset key.
A 08
If the error is permanent replace the circuit
board.
The processor RAM check is not correct.
A 09
Replace the circuit board.
The contents of the E2PROM are ruined. Re-
A 10
place the circuit board.
The values of the E2PROM do not match
A 12
those of the main software. Replace the circuit
board.
There has been a type "E" error that has not
A 13
been reset for more than 24 hours.
Internal software error. Replace the circuit
A 14
board.
Internal software error. Replace the circuit
A 15
board.
Internal software error. Press the reset key.
A 16
If the error is permanent replace the circuit
board.
Internal software error. Replace the circuit
A 17
board.
The flame was still detected after more than
10 seconds from the closure of the gas valve.
A 18
Press the reset key.
If the error is permanent replace the circuit
board.
The presence of a flame is detected more
A 19
than 10 seconds after the closure of the gas
valve.
Description
Error
type
Flame detected before the opening of the gas
valve. Press the reset key.
A 20
If the error is permanent replace the circuit
board.
Internal software error. Press the reset key.
A 32
If the error is permanent replace the circuit
board.
A 33
The fan does not spin at the proper speed.
The fan does not spin. Executes 4 cycles of 3
A 34
attempts each with A 34 resettable. The last
cycle triggers a permanent shutdown.
E 01
Delivery temperature probe open.
E 02
Return temperature probe open.
The delivery temperature, set on parameter 1,
E 03
was exceeded by 10°C for 5 seconds.
E 08
DHW tank temperature sensor open.
E 11
Delivery temperature probe short-circuit.
E 12
Return temperature probe short-circuit.
Incorrect temperature measurement. Replace
E 13
the circuit board.
Incorrect temperature measurement. Replace
E 14
the circuit board.
Incorrect temperature measurement. Check
E 15
the 16-pin J5 connector on the circuit board.
Replace the circuit board.
Incorrect temperature measurement. Replace
E 16
the circuit board.
E 18
DHW tank temperature sensor short circuited.
Not able to read the E2PROM. Replace the
E 19
circuit board.
Flame detected with gas valve closed. Internal
E 20
software error. Replace the circuit board.
E 21
Phase and neutral connections inverted.
E 23
Ground not connected. Poor grounding.
Flue temperature too high > 75°C.
E 35
Flue sensor short circuited.
E 36
Flue thermostat contact open.
Lack of water circulation. Water pressure too
E 37
low.
Communication problems. Replace the circuit
E 42
board.
Reset key error. The key was pressed more
E 51
than 5 times.
To reset the error cut off the main power.
U 10 (*) Low-temperature system delivery temperature
probe interrupted.
U 11 (*) Low-temperature system delivery temperature
probe short-circuit.
Delivery temperature >55°C (e.g. due to a
U 21 (*)
mixer valve fault).
U 99 (*) Electrical power supply interruption on the
multi-temperature kit's electronic board.
Errors associated with the multi-temperature control
(*)
board (where present and enabled)
If an error not present in the table is displayed, contact the
Technical Assistance Centre.
Description