Error List - Beretta Power Plus Box 1001 INT Installation Manual

Condensing
Table of Contents

Advertisement

11 ERROR LIST

A and E type errors possibly encountered with Power Plus Box 1001 are given in the tables below.
In this sense it should be specified that an E-type error (volatile error) is a fault which automatically disappears as soon
as the fault is resolved; whilst A type (non-volatile error) is a fault that will only disappear after resetting manually when
the problem has been resolved.
11 .1 Master board errors
Nr.
No. on the PC
A16
10
A18
12
A20
14
Nr.
No. on the PC
E02
51
E04
53
E18
67
E20
69
E23
28
E24
29
E25
0/30
E26
31
E32
33
E34
42
11 .2 Slave board errors
Nr.
No. on the PC
A01
1
A02
2
A04
4
A05
5
A06
6
A07
7
A08
8
A09
9
Cause
Internal error
Internal error
Internal error
Cause
NTC1 open (NTC1: delivery
sensor)
NTC3 open (NTC3: boiler
sensor)
NTC1 short circuiting (NTC1:
delivery sensor)
NTC3 short circuiting (NTC3:
boiler sensor)
Internal error
Internal error
Internal error
Internal error
Slaves not present
Internal 50HZ error
Cause
5 failed ignition attempts
Multiple unsuccessful
attempts due to flame
ionisation problems
Water side limit thermostat
(> 90°C) tripping, version
SCHEDA43
Gas valve coil interrupted.
False gas valve connector
contact.
Defective gas valve
connector.
Maximum temperature
thermostat tripped (> 90°C)
while burner was on.
No or bad ground connection.
BOARD 43 only
Internal error
Internal error
50Hz
Troubleshooting
Replace the Master card
Replace the Master card
Replace the Master card
Troubleshooting
Primary delivery sensor not connected or interrupted.
DHW sensor not connected or interrupted.
Primary circuit delivery sensor short circuit.
DHW sensor short circuiting.
Replace the Master card
Replace the Master card
Replace the Master card
Replace the Master card
Check that the bipolar switches of the individual units
are "ON".
Check the addresses on the slave.
Check the slave BUS connection.
Replace the Master card.
Replace the Slave card.
The main frequency is not 50Hz
Troubleshooting
Check that the gas tap is open.
Check for the presence of electric discharge between
the two ignition electrodes.
Check the ignition cable.
Do not open the gas valve.
Replace the electronic card (Slave).
Clean the electrodes.
Replace the igniter plug.
Replace the ignition cable.
Poor circulation in the primary circuit.
Limit thermostat defective.
Replace the gas valve.
Check the gas valve connector.
Replace the gas valve connector.
Poor circulation in the primary circuit.
Limit thermostat defective.
Check the earth connection.
Replace the Slave card.
Replace the Slave card.
Replace the Slave card.
The main frequency is not 50Hz
33