 Control and monitoring items with object types
Function name
2
Operation setting*
Operation mode
Temperature setting
Fan speed
R/C prohibition
Gateway
Representative error
Error code
Energy saving status/setting
Existence check
Temperature status/setting
Operation status/setting
Operation mode status/setting
Fan speed status/setting
Suction/Room temperature
Representative error
Error code
Temperature H/L limit status/
setting
Temperature limit validity
status/setting
Filter sign status/reset
Forced thermo off status/
3
setting*
Emergency stop
R/C prohibition status/setting
Vertical fan status/setting
Horizontal fan status/setting
Managed mode
Outdoor unit save status/
setting
Low noise operation status/
setting
Representative error
Error code
Forced off status/setting
3-9. BACnet gateway (Hardware: UTY-VBGX)
Category
Target
Monitor Control
Bat
Bat
Bat
Bat
Bat
GW
GW
GW
GW
In
In
In
In
In
In
In
In
In
In
In
In
In
In
In
In
In
Out
Out
Out
Out
Out
- (05-171) -
BACnet
object
Remarks
1
type*
BO
MO
AO
MO
MO
D
No monitor/control difference
BI
Gateway, Lon communication
Gateway, Lon communication
Error codes to signal gateway status
MI
will be agreed with FGL during
development.
BI/BO
BI
AI/AO
BI/BO
MI/MO
MI/MO
AI
BI
MI
H/L limit per 3 operation Mode:
AI/AO
HEAT, COOL-DRY, and AUTO
BI/BO
BI/BO
Only reset for control
BI / BO
BI
MI/MO
MI/MO
MI/MO
MI
MI/MO
MI/MO Monitor not supported by all
BI
MI
BI/BO