Fujitsu AJ 126LELDH Series Design & Technical Manual page 996

Hide thumbs Also See for AJ 126LELDH Series:
Table of Contents

Advertisement

• TM201 (CN411): Dry contact terminal
When a power supply is unnecessary at the input device you want to connect, use the Dry contact
terminal TM201 (CN411).
Connection example 1: When the switch is connected
*:
Short circuit detection resistance (R
Open circuit detection resistance (R
A twisted pair cable 0.33 mm
Connection example 2: When the electricity meter is connected
Connect the electricity meter to CH1. In this case, the use of CH2 is prohibited.
4-1. Touch panel controller
PCB
TM201
*
): ≤ 500 Ω
ON
): ≥ 100 kΩ
OFF
2
(22 AWG) should be used. (Maximum cable length: 25 m)
PCB
TM201
- (08-28) -
PCB
PCB
4. Controller