Fujitsu AJ 126LELDH Series Design & Technical Manual page 906

Hide thumbs Also See for AJ 126LELDH Series:
Table of Contents

Advertisement

Function
Function
number
Fan setting
when
cooling
49
thermostat
OFF
Switching
functions for
60
external
inputs
Auto mode
68
type
Deadband
69
value
2-10. Function details
Factory
Setting number
setting
Follow the setting
00
on the remote
controller
01
Stop
Forced thermostat
00
off
01
02
03
04
forbidden
05
06
07
08
Refrigerant leak
09
detection
Single setpoint
00
auto mode
(traditional)
Dual setpoint auto
01
mode
00
0 °C
01
0.5 °C
02
1.0 °C
03
1.5 °C
04
2.0 °C
05
2.5 °C
06
3.0 °C
07
3.5 °C
08
4.0 °C
09
4.5 °C
When set "00", indoor unit is continued operation
based upon central remote controller or
individual controller set.
Once indoor unit received signal from external
controller, indoor unit changed fan mode forcibly.
When set "01", indoor unit is continued operation
based upon central remote controller or
individual controller set.
Once indoor unit received signal from external
controller, indoor unit stop forcibly.
Connection of the wired remote controller (2-wire
type or 3-wire type) and switching its thermistor
are necessary.
Setting is required when connecting a refrigerant-leak
detection device.
For details, refer to
OUTPUT".
Switches the setting method of auto mode to single or
dual (cooling/heating).
For heat pump systems, it is necessary to set the
master indoor unit by using wired remote controller.
NOTE: Auto mode type will be usable provided
that the corresponding operating device is
connected.
Choose the minimum temperature between cooling
and heating settings (deadband) for dual setpoint
auto mode (function number 68).
NOTE: Deadband value will be usable provided
that the corresponding operating device is
connected.
- (07-110) -