Checklists
Table 27: Proof test checklist
Configuration
Safe CLOSING (Safe ESD in direction CLOSE)
1. Is actuator in mid-position or at sufficient distance
from the end positions?
Safe ESDa
Safe ESDb
2.
and
set to 0 V (low)?
➥ Check actuator reaction:
Safety operation initiated?
3. Wait until actuator limit switch trips.
➥ Check actuator reaction:
Safety operation stopped when reaching limit switch
CLOSED?
4.
Safe ESDa
and
Safe ESDb
set to +24 V DC (high)?
☒ ✓ = Executed
☒ Yes = Condition met
☒ No = Condition not met
If the answer to one of the questions is no, the safety instrumented system must be checked.
11.2.7.
Safe ESD reaction to "Forced torque seating in end position" (torque after limit evaluation)
Table 28: Proof test checklist
Configuration
Safe CLOSING (Safe ESD in direction CLOSE)
1. Actuator operated to end position CLOSED via
standard controls (until limit switch in end position
trips)?
2. Switch compartment opened?
3. + 4. Torque switch CLOSE operated and safety
operation initiated for operated switch?
(Test button [1] turned in direction of the TSC arrow?)
Safe ESDa
Safe ESDb
and
to 0 V (low)?
➥ Check actuator reaction:
Safety operation not initiated?
➥ Check SIL module signal behaviour:
No SIL fault signal?
SIL failure
output (NC contact) = open)
5.
Safe ESDa
and
Safe ESDb
set to +24 V DC (high)?
6. Switch compartment closed?
☒ ✓ = Executed
☒ Yes = Condition met
☒ No = Condition not met
If the answer to one of the questions is no, the safety instrumented system must be checked.
11.2.8.

Safe ESD reaction to "No seating"

46
input signals
Yes
No
Yes
No
input signals
Proof test checklist for version or configuration:
Actuator with electromechanical control unit
One of the following safety functions:
-
Safe ESD function: "Safe CLOSING" (Safe ESD in direction CLOSE)
-
Safe ESD function "Safe OPENING" (Safe ESD in direction OPEN)
"SIL seating" configuration
= Forced torque seating in end position"
Also valid for combination of SafeESD with Safe STOP.
input signals set
Yes
No
Yes
No
input signals
Proof test checklist for version or configuration:
Actuator with electromechanical control unit:
SQ 05.2
Configuration
Safe OPENING (Safe ESD in direction OPEN)
1. Is actuator in mid-position or at sufficient distance
from the end positions?
Safe ESDa
Safe ESDb
2.
and
set to 0 V (low)?
➥ Check actuator reaction:
Safety operation initiated?
3. Wait until actuator limit switch trips.
➥ Check actuator reaction:
Safety operation stopped when reaching limit switch
OPEN?
4.
Safe ESDa
and
Safe ESDb
set to +24 V DC (high)?
Configuration
Safe OPENING (Safe ESD in direction OPEN)
1. Actuator operated to end position OPEN via
standard controls (until limit switch in end position
trips)?
2. Switch compartment opened?
3. + 4. Torque switch OPEN operated and safety op-
eration initiated for operated switch?
(Test button [2] turned in direction of the TSO arrow?)
Safe ESDa
Safe ESDb
and
to 0 V (low)?
➥ Check actuator reaction:
Safety operation not initiated?
➥ Check SIL module signal behaviour:
No SIL fault signal?
SIL failure
output (NC contact) = open)
5.
Safe ESDa
and
Safe ESDb
set to +24 V DC (high)?
6. Switch compartment closed?
Part-turn actuators
SQ 14.2/SQR 05.2
SQR 14.2
input signals
input signals
input signals set
input signals
Yes
No
Yes
No
Yes
No
Yes
No