Applications (Environmental Conditions) - AUMA SQ 05.2-SQ 14.2 Manual

Part-turn actuators
Table of Contents

Advertisement

Part-turn actuators
SQ 05.2
SQ 14.2/SQR 05.2
Information
3.3.

Applications (environmental conditions)

SQR 14.2
Table 4: For actuators with electromechanical control unit:
Configuration
Short description
SIL seating type
1: No seating
No seating by limit or torque switches dur-
ing safety operation
2: Forced torque seat-
Safety operation is stopped if both limit and
ing in end position
torque switches trip simultaneously
3: Forced limit seating
Safety operation is stopped by limit switch
in end position
tripping
4: Limit seating with
Safety operation is stopped by tripping the
overload protection
limit switches and/or the torque switches
(overload protection).
Table 5: For actuators with electronic control unit MWG
Configuration
Short description
SIL seating type
1: No seating
No seating by limit or torque switches dur-
ing safety operation
Table 6: For actuators with electronic control unit MWG including limit switches
Configuration
Short description
SIL seating type
3: Forced limit seating
Safety operation is stopped by limit switch
in end position
tripping
Configuration options for motor protection assessment
Table 7: Configuration options for motor protection assessment
Configuration
Short description
SIL motor protection
Active
Tripping of the motor protection (thermal fault) stops or prevents safety
operation
Inactive
Motor protection has no impact on the safety operation
"SIL motor protection" = "inactive" configuration is only set if explicitly required. The
version does not meet the Ex approval requirements.
When specifying and using the actuators within safety instrumented systems, make
sure that the permissible service conditions and the EMC requirements by the
peripheral devices are met. Service conditions are indicated in the technical data
sheets:
Enclosure protection
Corrosion protection
Ambient temperature
Vibration resistance
If the actual ambient temperatures exceed an average of +40 °C, the lambda values
have to be incremented by a safety factor. For an average temperature of +60 °C,
this factor is specified to 2.5.
For environmental test, actuator and actuator controls were subjected to the following
standards:
Dry heat: EN 60068-2-2
Damp heat: EN 60068-2-30
Cold: EN 60068-2-1
Architecture, configuration and applications
Configuration
Type of seating
Standard controls
Freely selectable
Torque seating
Limit seating
Limit seating
Configuration
Type of seating
Standard controls
Freely selectable
Configuration
Type of seating
Standard controls
Limit seating
9