Safe Esd Reaction To "Limit Seating With Overload Protection - AUMA SQ 05.2-SQ 14.2 Manual

Part-turn actuators
Table of Contents

Advertisement

Part-turn actuators
SQ 05.2
SQ 14.2/SQR 05.2
Test procedure
8.4.4.
Safe ESD reaction to "Limit seating with overload protection" (limit and/or torque evaluation):
check
Configuration
Test procedure
SQR 14.2
Proof test (motor prot.) M1021
Simulation value: Thermal test
Figure 11: Display indication on local controls
The simulation (active/inactive) is activated and deactivated by push button Ok.
A dot on the display indicates that the simulation is active.
Black dot (●): Motor protection simulation active (thermal fault)
White dot (○): Signal not active
1.
Operate actuator in mid-position or at sufficient distance from the end positions.
2.
Set selector switch to position 0 (OFF).
3.
Change to main menu and select the Thermal test simulation value via the
Proof test (motor prot.) M1021 parameter (Do not yet activate simulation: white
dot).
4.
Set
and
Safe ESDa
Safety operation is initiated.
5.
Activate motor protection simulation: Press push button Ok (black dot)
Safety function is correct, if:
-
For SIL motor protection" = active configuration:
-
Safety operation is stopped.
-
A SIL fault signal is issued via the
-
For SIL motor protection" = inactive configuration:
-
Safety operation is not stopped.
-
Nevertheless, a SIL fault signal is issued via the
6.
Set
and
Safe ESDa
test.
7.
Reset simulation or exit the simulation menu and reset selector switch to initial
position.
This test is required for the following versions or configurations:
Actuator with electromechanical control unit
One of the following safety functions:
-
Safe ESD function: "Safe CLOSING" (Safe ESD in direction CLOSE)
-
Safe ESD function "Safe OPENING" (Safe ESD in direction OPEN)
"SIL seating" configuration
= Limit seating with overload protection"
(Safety operation is stopped by limit switch tripping and/or torque switch tripping
(overload protection).
During the test, the reaction of the Safe ESD function to limit switch tripping and/or
torque switch tripping during safety operation is checked.
During Safe ESD operation, the actuator has to stop when reaching the position set
via limit switching. Safe ESD operation must also be stopped if the tripping torque
set via the torque switching is exceeded.
The red test buttons [1] and [2] of the control unit are used for the test. These can
be used to operate the switches manually.
input signals to 0 V (low).
Safe ESDb
SIL failure
input signals to +24 V DC (high) after the
Safe ESDb
Tests and maintenance
output.
SIL failure
output.
27