Sil Configuration Warning; Backlight - AUMA SQ 05.2-SQ 14.2 Manual

Part-turn actuators
Table of Contents

Advertisement

Part-turn actuators
SQ 05.2
SQ 14.2/SQR 05.2
Information
6.2.

SIL configuration warning

6.3.

Backlight

SQR 14.2
Figure 10: Signal: Safety function active
As soon as a safety function is active (SIL function active indication), the actuator is
controlled via the safety PLC and the SIL module. For "normal control" (standard
PLC), controls are therefore "Not ready REMOTE".
In combination with the safety functions, the following configurations or settings of
standard controls may have an impact on the standard functions:
Self-retaining Local M0076 = OPEN/CLOSE
Self-retaining Remote M0100 = OPEN/CLOSE
If one of these configurations is selected in the standard controls, the device generates
the SIL config. warning.
In standard operation, display backlight of actuator controls is white. In the event of
a fault, the display backlight is red. The red backlight does NOT refer to the safety
function status but to the faults referred to as "faults" in the Manual (Operation and
setting) AUMATIC AC 01.2.
Indications on display
19