11.2.10. Combination Of Safe Esd And Safe Stop - AUMA SQ 05.2-SQ 14.2 Manual

Part-turn actuators
Table of Contents

Advertisement

Checklists
Table 30: Proof test checklist
Safe stop in direction OPEN
Safe STOP OPEN
1. Is actuator in mid-position or at sufficient distance
from the end positions?
2. Operation command via standard controls in direc-
tion OPEN executed?
Safe STOP CLOSE
3.
(low)?
➥ Check actuator reaction:
Does actuator continue its operation in direction
OPEN?
➥ Check SIL module signal behaviour:
No SIL fault signal?
SIL failure
output (NC contact) = open)
4.
Safe STOP OPEN
input signal set to 0 V (low)?
➥ Check actuator reaction:
Does actuator stop?
➥ Check SIL module signal behaviour:
No SIL fault signal?
SIL failure
output (NC contact) = open)
Safe STOP OPEN
5.
CLOSE
input signals set to +24 V DC (high)?
☒ ✓ = Executed
☒ Yes = Condition met
☒ No = Condition not met
If the answer to one of the questions is no, the safety instrumented system must be checked.

11.2.10. Combination of Safe ESD and Safe STOP

Table 31: Proof test checklist
Safe stop in direction CLOSE
Safe CLOSING (Safe ESD in direction CLOSE)
1. Is actuator in mid-position or at sufficient distance
from the end positions?
Safe STOP CLOSE
2
(low)?
Safe ESDa
Safe ESDb
3.
and
set to 0 V (low)?
➥ Check actuator reaction:
Safety operation in direction CLOSE initiated?
➥ Check SIL module signal behaviour:
No SIL fault signal?
SIL failure
output (NC contact) = open)
Safe ESDa
Safe ESDb
4.
,
OPEN
and
Safe STOP CLOSE
to +24 V DC (high)?
☒ ✓ = Executed
☒ Yes = Condition met
☒ No = Condition not met
If the answer to one of the questions is no, the safety instrumented system must be checked.
48
input signal set to 0 V
Safe STOP
and
Proof test checklist for version or configuration:
One of the following Safe ESD safety functions with any seating configuration:
-
Safe ESD function: "Safe CLOSING" (Safe ESD in direction CLOSE)
-
Safe ESD function: "Safe OPENING" (Safe ESD in direction OPEN)
Safe STOP function
input signal set to 0 V
input signals
Safe STOP
,
input signals set
SQ 05.2
Safe stop in direction CLOSE
Safe STOP CLOSE
1. Is actuator in mid-position or at sufficient distance
from the end positions?
2. Operation command via standard controls in direc-
tion CLOSE executed?
Safe STOP OPEN
3.
Yes
➥ Check actuator reaction:
No
Does actuator continue its operation in direction
CLOSE?
Yes
➥ Check SIL module signal behaviour:
No SIL fault signal?
No
SIL failure
4.
Safe STOP CLOSE
(low)?
Yes
➥ Check actuator reaction:
No
Does actuator stop?
Yes
➥ Check SIL module signal behaviour:
No
No SIL fault signal?
SIL failure
Safe STOP OPEN
5.
CLOSE
input signals set to +24 V DC (high)?
Safe stop in direction OPEN
Safe OPENING (Safe ESD in direction OPEN)
1. Is actuator in mid-position or at sufficient distance
from the end positions?
Safe STOP OPEN
2
Safe ESDa
3.
set to 0 V (low)?
Yes
➥ Check actuator reaction:
No
Safety operation in direction OPEN initiated?
➥ Check SIL module signal behaviour:
Yes
No
No SIL fault signal?
SIL failure
Safe ESDa
4.
,
OPEN
and
Safe STOP CLOSE
to +24 V DC (high)?
Part-turn actuators
SQ 14.2/SQR 05.2
input signal set to 0 V (low)?
output (NC contact) = open)
input signal set to 0 V
output (NC contact) = open)
Safe STOP
and
input signal set to 0 V (low)?
Safe ESDb
and
input signals
output (NC contact) = open)
Safe ESDb
Safe STOP
,
input signals set
SQR 14.2
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No