Mitsubishi Electric FR-E720-600 Instruction Manual page 176

Hide thumbs Also See for FR-E720-600:
Table of Contents

Advertisement

Frequency setting by analog input (terminal 2, 4)
(b) Method to adjust any point without application of a voltage (current) to across terminals 2-5 (4-5)
(To change from 4V (80%) to 5V (100%))
Operation
1.
Confirmation of the RUN indication and operation
mode indication
The inverter should be at a stop.
The inverter should be in the PU operation mode.
(Use
)
2.
Press
to choose the parameter setting
mode.
3.
Turn
until
4.
Turn
until
5.
Turn
until
Set to C4 Terminal 2 frequency setting gain.
6.
Press
to display the analog voltage
(current) value (%).
7.
Turn
to set gain voltage (%).
"0V(0mA) is 0%, 10V(5V, 20mA) is 100%"
REMARKS
The current setting at the instant of turning
displayed.
You can not check after performing operation in step 7.
8.
Press
to set.
Turn
Press
Press
REMARKS
By pressing
You can not check after performing operation in step 7.
174
appears.
appears.
(
) appears.
Flicker...Parameter setting complete!!
to read another parameter.
to return to the
indication (step 4).
twice to show the next parameter (
after step 6, you can confirm the current frequency setting bias/gain setting.
Display
PRM indication is lit.
(The parameter number read previously appears.)
C0 to C41 setting
is enabled.
Terminal 2 input is
Terminal 4 input
selected
is selected
Analog voltage (current) value (%)
across terminals 2-5 (across
terminals 4-5)
The gain frequency is reached
when the analog voltage (current)
value across terminals 2-5 (across
terminals 4-5) is 100%.
is
A
Terminal 2 input
is selected
(Adjustment completed)
).
Terminal 4 input
is selected