Mitsubishi Electric FR-E720-600 Instruction Manual page 142

Hide thumbs Also See for FR-E720-600:
Table of Contents

Advertisement

Function assignment of external terminal and control
(3) Fault output signal (ALM signal)
Inverter fault occurrence
(Trip)
Output
frequency
ALM
OFF
ON
RES
ON OFF
Reset ON
REMARKS
The ALM signal is assigned to the ABC contact in the default setting. By setting "99 (positive logic) or 199 (negative logic) in
Pr.190 to Pr.192 (output terminal function selection), the ALM signal can be assigned to the other signal.
Refer to page 272 for the inverter fault description.
(4) Fault output 3 (power-off signal) (Y91 signal)
The Y91 signal is output at occurrence of a fault attributable to the failure of the inverter circuit or a fault caused by a wiring
mistake.
When using the Y91 signal, set "91 (positive logic)" or "191 (negative logic)" to any of Pr.190 to Pr.192 (output terminal function
selection) to assign the function to the output terminal.
The following table indicates the faults that will output the Y91 signal. (Refer to page 271 for the fault description.)
Operation Panel
Indication
E. BE
E.GF
E.LF
E.PE
E.PE2
/
E. 6/
E. 7/
/
E.CPU
E.IOH
REMARKS
At occurrence of output side earth (ground) fault overcurrent (E.GF), overcurrent trip during acceleration(E.OC1) may be
displayed. At this time, the Y91 signal is output.
Parameters referred to
Pr. 13 Starting frequency
140
Reset processing
(about 1s)
Name
Brake transistor alarm detection
Output side earth (ground) fault overcurrent
Output phase loss
Parameter storage device fault
Internal board fault
CPU fault
Inrush current limit circuit fault
Refer to page 105
If the inverter comes to trip, the ALM signal is output.
Time

Advertisement

Table of Contents
loading

Table of Contents