NOTE
Set Pr. 267 and a voltage/current input switch correctly, then input an analog signal in accordance with the setting.
Incorrect setting as in the table below could cause component damage. Incorrect settings other than below can
cause abnormal operation.
Setting Causing Component Damage
Switch setting
I (current input)
V (voltage input)
Refer to the following table and set Pr. 73 and Pr. 267.
(
indicates main speed setting)
Pr.73
Terminal 2
Setting
Input
0
0 to 10V
1
0 to 5V
(initial value)
10
0 to 10V
11
0 to 5V
0
1
(initial value)
10
11
Turn the AU signal on to make terminal 4 valid.
The terminal used for the AU signal input, set "4" in Pr. 178 to Pr. 184 (input terminal function selection) to assign functions.
NOTE
Turn the AU signal on to make terminal 4 valid.
Make sure that the parameter and switch settings are the same. Different setting may cause a fault, failure or
malfunction.
Use Pr. 125 (Pr. 126) (frequency setting gain) to change the maximum output frequency at input of the maximum output
frequency command voltage (current). At this time, the command voltage (current) need not be input.
Also, the acceleration/deceleration time, which is a slope up/down to the acceleration/deceleration reference
frequency, is not affected by the change in Pr. 73 setting.
Changing the terminal assignment using Pr. 178 to Pr. 184 (input terminal function selection) may affect the other
functions. Make setting after confirming the function of each terminal.
Forward rotation
STF
SD
0 to 5VDC
10
Frequency setting
2
5
Connection diagram using terminal 2 (0 to 5VDC)
Forward rotation
0 to 10VDC
Frequency
Voltage input
setting
equipment
Connection diagram using terminal 2 (0 to 10VDC)
REMARKS
The wiring length of the terminal 10, 2, 5 should be 30m (98.42feet) maximum.
Frequency setting by analog input (terminal 2, 4)
Terminal input
This could cause component damage to the analog signal output circuit of
Voltage input
signal output devices.
(electrical load in the analog signal output circuit of signal output devices increases)
This could cause component damage of the inverter signal input circuit.
Current input
(output power in the analog signal output circuit of signal output devices increases)
Terminal 4 Input
AU signal
OFF
ON
(2)
Perform operation by analog input selection.
Inverter
The frequency setting signal inputs 0 to 5VDC (or 0 to 10VDC) to
across the terminals 2-5. The 5V (10V) input is the maximum output.
The power supply 5V can be input by either using the internal power
supply or preparing an external power supply. Prepare an external
power supply to input the power supply 10V. For the built-in power
supply, terminals 10-5 provide 5VDC output.
Terminal
Inverter
STF
SD
When inputting 10VDC to the terminal 2, set "0" or "10" in Pr. 73. (The
initial value is 0 to 5V)
2
Setting "1 (0 to 5VDC)" or "2 (0 to 10VDC)" in Pr. 267 and a voltage/
5
current input switch in the OFF position changes the terminal 4 to the
voltage input specification. When the AU signal turns on, the terminal
4 input becomes valid.
Operation
According to the Pr. 267 setting
0:4 to 20mA (initial value)
1:0 to 5V
2:0 to 10V
Inverter Built-in
Power Supply
Voltage
10
5VDC
Reversible
Operation
Not function
Yes
Not function
Yes
- : invalid
Frequency
Pr.73
Setting
(terminal 2 input
Resolution
power)
0.030Hz/60Hz
0 to 5VDC input