Mitsubishi Electric FR-E720-600 Instruction Manual page 190

Hide thumbs Also See for FR-E720-600:
Table of Contents

Advertisement

Selection of operation mode and operation location
(6) PU/external combined operation mode 1 (setting "3")
Three-phase AC
power supply
Forward rotation start
Reverse rotation start
(7) PU/external combined operation mode 2 (setting "4")
Three-phase AC
power supply
Frequency setting
potentiometer
188
Inverter
R/L1
U
S/L2
V
T/L3
W
STF
STR
SD
Operation panel
Set frequency
Inverter
R/L1
U
S/L2
Motor
V
T/L3
W
10
2
5
Operation panel
,
Select the PU/external combined operation mode 1
when
applying
operation panel or parameter unit (FR-PU04/FR-
PU07) and inputting the start command with the
external start switch.
Select "3" for Pr. 79. You cannot change to the other
operation mode.
When a frequency is applied from the external signal
by multi-speed setting, it has a higher priority than the
frequency command from the PU. When AU is on, the
command signal to terminal 4 is used.
Motor
Select the PU/external combined operation mode 2 when
applying
frequency
potentiometer, multi-speed or JOG signal and inputting the
start command by key operation of the operation panel (FR-
PU04/FR-PU07).
Select "4" for Pr. 79. You cannot change to the other
operation mode.
frequency
command
from
command
from
the
the
external