Programming
Pressing the down arrow key displays additional zone types as indicated in the following table.
Combo w/AutoResettable Superv
Table Footnote
1. Activation of a Manual Release Switch will override Predischarge Delay and
2. AutoResettable means that a device with this type code, when activated, will
3. Disable Release allows the installer to disable the releasing solenoids during
4. Activation of an Abort Release Switch during system normal operation (non-
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
52
Zone Type
Pull-Station
1
Manual Release
Normally Open Contact
N/A
N/A
Waterflow
Waterflow NS (nonsilenceable)
Combo
2
2-Wire Smoke
2-Wire Heat
Linear Heat
N/A
N/A
Fire
Low Pressure
2
Low Pressure AutoResettable
High Pressure
2
High Pressure AutoResettable
3
Disable Release
Supervisory
2
Supervisory AutoResettable
4
Abort Release Switch
N/A
override an active Abort Release Switch, resulting in an immediate agent release.
automatically reset when the corresponding condition is cleared.
system testing. Disable Release will only work when the system is not in alarm.
alarm) results in an audible and visual indication at the FACP.
Table 3.1 Zone Types
Action When Activated
Fire Alarm
Fire Alarm
Fire, nonsilenceable
Fire/Supervisory
Fire/Supervisory, nonlatching
Fire Alarm
Fire Alarm
Fire Alarm
Fire Alarm
Supervisory, latching
Supervisory, nonlatching
Supervisory
Supervisory, nonlatching
Supervisory, nonlatching (disables Release Circuits)
Supervisory, latching
Supervisory, nonlatching
Supervisory, nonlatching
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008
Master Programming Level
Fire
Fire

Advertisement